System information

TrueAlarm Information Details
True Alarm sensor data can be displayed on the
system LCD, on a remote maintenance terminal, or
printed on a remote printer. With the proper operator
access, a TrueAlarm Service Report can be generated to
list the specific details of each TrueAlarm device. This
report, as well as the Status Report can either be displayed
on the remote maintenance terminal or captured
permanently by using a remote 80 character printer.
The figures below illustrate the format provided on either
the remote maintenance terminal or a printer. This
information is available at the system LCD by identifying
the specific point of interest and reading one point at a
time.
Compatible RS-232 devices include the Simplex model
4190-9006 Terminal and the Simplex model 4190-9007,
80 column, 24 pin dot matrix printer. (The 2190-9039,
24 VDC, 40 column printer is compatible with the 4010
for event printing only.)
(Contact Simplex for information on the complete line of
TrueAlarm analog sensing products.)
Remote Maintenance
Terminal (Simplex
model 4190-9006)
4010 Fire Alarm
Control Panel
RS-232 connections, one per device
Remote Printer
(Simplex model 4190-9007)
TIME: 1:56:10 customtitle USER:1
DATE: W ED 9 O CT 96 Port 1 Card 5 A ACCESS: 1
ALARMS : 2 TROUBL ES: 0 SUPERV ISORIE S: 0
1:42:05 PM WE D 9 OC T 96 1 ST FLO OR EAS T WING
SMOKEDETECTOR ALARM
1:55: 16 PM W ED 9 O CT 96 1ST FL OOR EA ST WING
PULLSTATION ALARM
PF1=Ack, PF2= Silence, PF3= SystemReset, PF4= Login>
FIRE ALARM
CONT ROL
DISCONNE C T
POWER BEFORE
SERVIC ING
CAUT ION
** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
SUPV
ACK
SYSTEM
SUPERV I SO RY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENC ED
SYSTEM
RESE T
AC
POWER
4010 Fire Alarm Control Panel
RS-232 Connection Options
Simplex Time Recorder Co. 4 S4010-0001-4 4/00
Simplex 4010 Fire Alarm System Page 1
REPORT 4 : TrueAlarm Service Report 2:56:09 pm Mon 6-Mar-00
Dev
Num Custom Label
Alarm
at:
Avg
val
Current/
% alarm
Peak/
% alarm
State
1 ANALOG PHOTO - CLEAN ROOM 0.5/ 83 67 68/ 1% 72/ 10% NOR
2 ANALOG ION - CLEAN ROOM 1.3/209 94 97/ 2% 101/ 1% NOR
3 ANALOG PHOTO - MAIN LOBBY 2.5/185 117 117/ 0% 125/ 42% NOR
4 ANALOG PHOTO - CONFERENCE ROOM 1 2.5/161 93 93/ 0% 93/ 0% NOR
10 HEAT DETECTOR - GARAGE 135F/253 –-- 63/-67F 66/ 69F NOR
11 ANALOG PHOTO - KITCHEN 3.7/216 116 116/ 1% 110/ 36% NOR
END OF REPORT
Typical TrueAlarm Service Report Information Printout and/or Maintenance Terminal Screen
Simplex 4010 Fire Alarm System Page 1
REPORT 3 : TrueAlarm Status Report 2:43:03 pm Mon 6-Mar-00
Zone
Name Custom Label
Sensi-
tivity Device Status
Almost
Dirty
M1-1 ANALOG PHOTO CLEAN ROOM 0.5 % NORMAL
M1-2 ANALOG ION CLEAN ROOM 1.3 % NORMAL
M1-3 ANALOG PHOTO MAIN LOBBY 2.5 % NORMAL *YES*
M1-4 ANALOG PHOTO CONFERENCE ROOM 1 2.5 % NORMAL
M1-10 HEAT DETECTOR GARAGE 135 F NORMAL
M1-11 ANALOG PHOTO KITCHEN 3.7 % NORMAL *YES*
END OF REPORT
Typical TrueAlarm Status Report Information Printout and/or Maintenance Terminal Screen
TrueAlarm Status and Service Report Samples