System information
Features
Up to 250 addressable TrueAlarm or IDNet points**
Four, 2 A notification appliance circuits (NACs)
with solid state current protection
UL listed to Standard 864
Installation convenience features:
• Power-limited design with electronic modules
contained on one-piece chassis
• Up-front terminal blocks for wiring access
• Compact NEMA 1 rated cabinet is available in beige or
red and can be pre-shipped for early installation
Setup, programming, and maintenance features:
• Device level ground fault search, locate and isolate
• Auto Program, automatic module and device
programming for general alarm operation
• TrueAlarm individual analog sensing with front panel
information and selection access**
• “Dirty” TrueAlarm sensor maintenance alerts, service
and status reports including “almost dirty”
• Default TrueAlarm sensor device type operation
• Duplicate address error detection
• Front panel or PC programming
• TrueAlarm sensor peak value performance report
• WALKTEST™ silent or audible system test
†
• Software verification simulation mode
Supports the following IDNet devices** :
• Addressable manual stations
• Quad-state zone adapter modules (ZAMs) for initiating
device monitoring
• IDNet ground fault/short circuit isolator base for
TrueAlarm sensors
• Quad-state line powered individual addressable
modules (IAMs) for initiating device monitoring and
relay control
Available option modules include:
• Simplex 4120 Network, DACT, or City interface
• Equipment for Suppression Release Applications
(refer to data sheet S4010-0003)
• RS-232 ports for printers or maintenance terminal
• Class A NAC adapter module
• Additional power supply
Compatible with Simplex:
• TrueAlert™ Addressable Controllers and NAC power
extenders (IDNet controlled and conventional)
• 4003 Voice Control Panel
• 4081 Battery Cabinet with charger for 50 Ah batteries
† Simplex WALKTEST system test is protected under U.S. patent # 4,725,818.
4010 TrueAlarm Fire Alarm Control Panel
Description
TrueAlarm fire alarm control panels have the ability
to provide location accuracy for monitoring and control.
When equipped with TrueAlarm analog sensing for
smoke and heat detection, the processing power of the
control panel also has the ability to analyze conditions at
each location to provide accurate detection with
significantly reduced maintenance costs.
The Simplex 4010 TrueAlarm Fire Alarm Control Panel
has been specifically designed to provide addressable
operation and analog detection in a cost-effective package
for application sizes that previously were considered only
appropriate for conventional zoned monitoring.
Installation and Service Ease. The 4010 mounts on a
single chassis for quick installation and removal.
Terminal blocks are large and up-front for easy access
and inspection. Optional modules are easily and quickly
installed and programmed as required.
The 4010 cabinet provides convenient stud markers for
drywall thickness and nail-hole knockouts for quicker
mounting. Smooth cabinet surfaces are provided for
locally cutting conduit entrance holes exactly where
required. 4010 cabinets and electronics can be ordered
separately, allowing early cabinet installation.
Ground Fault Assistance. Ground fault problems
often occur during installation. The 4010 provides
isolating circuitry and software-controlled sequencing to
isolate ground faults to specific identified locations. This
assistance helps the installer to accurately locate the
wiring problem for quicker repair.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7170-0026:226 for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Accepted for
use – City of New York Department of Buildings – MEA35-93E. Additional listings may be
applicable, contact Simplex for the latest status.
** Simplex TrueAlarm analog smoke detection and IDNet addressable devices are
protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,543,777;
5,400,014; 5,552,765; 5,552,763; DES. 377,460.
TrueAlarm
®
Fire Alarm Controls
UL, ULC Listed; FM, CSFM, and Model 4010 Fire Alarm Control Panel for
NYC, MEA Approved* TrueAlarm
®
Analog Sensors and IDNet™ Addressable Devices
© 2000 Simplex Time Recorder Co. All rights reserved. S4010-0001-4 4/00