Installation guide

6
Power-limited
Wiring Guidelines
Non-power limited field wiring (AC power, batteries, City connection) must be installed and
routed in the shaded areas shown in Figure 2.
Power-limited field wiring must be installed and routed in the non-shaded areas shown in
Figure 2, with the exception of City wiring.
Excess slack should be kept to a minimum inside the back box enclosure. The wiring should
be neatly dressed and bundled together using the wire ties provided with the equipment.
Anchor power-limited wiring to tie points, as shown in Figure 2.
Figure 2. Power-limited wiring
Tie the wiring located between bays to the internal wiring troughs, if applicable.
When powering remote units or switching power through relay contacts, power for these
circuits must be provided by a power-limited power supply that is listed for fire-protective
signaling use.