Installation guide
6
Power-limited
Wiring Guidelines
•
Non-power limited field wiring (AC power, batteries, City connection) must be installed and
routed in the shaded areas shown in Figure 2.
•
Power-limited field wiring must be installed and routed in the non-shaded areas shown in
Figure 2, with the exception of City wiring.
•
Excess slack should be kept to a minimum inside the back box enclosure. The wiring should
be neatly dressed and bundled together using the wire ties provided with the equipment.
Anchor power-limited wiring to tie points, as shown in Figure 2.
Figure 2. Power-limited wiring
•
Tie the wiring located between bays to the internal wiring troughs, if applicable.
•
When powering remote units or switching power through relay contacts, power for these
circuits must be provided by a power-limited power supply that is listed for fire-protective
signaling use.
&21'8,7(175$1&(
)2512132:(5
/,0,7(':,5,1*
12132:(5
/,0,7(':,5,1*
7,(32,17
/2&$7,210$<9$5<
32:(5/,0,7('
:,5,1*
&21'8,7(175$1&(
)2532:(5/,0,7('
:,5,1*
Power-Limited Wiring Guidelines