LOAD BANK MANUAL • Merlin 150-300 Load Bank • page 7 of 15
LOAD O VER V OLTAGE
D ETECTION S UBSYSTEM
The over voltage detection network is
activated only when a high (greater
than 380V) voltage test source is ap-
plied and the “Voltage Selector” switch
(S1) is incorrectly placed in the “Low
Voltage” position. When the switch is
in the “Low Voltage” position load bus
voltage is supplied to the Over Voltage
Relay (OVR) via Transformer T1. When
load voltage becomes great enough the
Over Voltage Relay (OVR) energizes.
OVR contacts 4–7 close and illuminate
the “Over Voltage” lamp. OVR contacts
9–3 open and interrupt the circuit to
the Master Load switch (S2). The load
cannot be re-applied until the control
power system is reset and the load
voltage selector switch is placed in the
high voltage position.
LOAD ELEMENTS
The Merlin Load Bank utilizes spe-
cially designed, “Powr-Web” resistive
elements. The elements are rigidly
supported by high-temperature, ceram-
ic-clad, stainless-steel rods. Element-
to-element short circuits are virtually
eliminated. The load elements are pro-
tected by 200KAIC, 600VAC fuses.
Do Not allow the Load Bank to
operate unattended for extended
periods.
Part of Typical Control Section Drawing