Specifications

Simplex, Inc., 5300 Rising Moon Road, Springfi eld, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
Merlin-150-300c.indd • © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Merlin 150-300 Load Bank • page 3 of 15
The Local Control Panel is comprised
of the following components:
1. Voltmeter, Ammeter, and
Frequency Meter
2. Control Power, Volt-Ammeter,
Ammeter Range Selector, Control
Power Selector, and Voltage
Selector switches
3. Cooling Failure and Load Over
Voltage lamps
4. Ammeter Range Selector Switch
5. Alarm Reset pushbutton
6. Master Load and load step
switches
The resistive load elements in this
Load Bank are cooled by a horizontal
forced air system. The load system is
connected to the test source via the
load cables.
Part of Typical Local Control Detail Drawing
This Load Bank is equipped with the
following automatic safety systems
which de-energize all load steps when
any condition is present which could
damage the Load Bank or present a
safety hazard to the operator:
1. The Cooling Failure Subsystem de-
energizes any load applied when
cooling of the load elements becomes
inadequate due to fan failure, high
intake air temperature, or high ex-
haust temperature.
2. The Load Power Over Voltage Failure
System removes all load from the test
source in the event the Load voltage
selector switch is in the low voltage
position (less than 240V), and a high
test source voltage (greater than
480V) is applied.