LOAD BANK MANUAL • Merlin 150-300 Load Bank • page 9 of 15
LOAD OVER VOLTAGE
INDICATED
1. Load Voltage Selector switch
incorrectly positioned
COOLING FAILURE
INDICATED
1. Restriction of air
(intake or exhaust)
2. Fan pressure switch inoperative
3. Overtemperature sensor failure
4. Alarm Reset pushbutton not engaged
TEST METERS DO NOT
OPERATE PROPERLY
1. Meter voltage switch failure
2. Meter multiplier resistor inoperative
3. Improper positioning of meter volt-
age selector switch
4. Current transformer or current
transformer wiring failure
5. Test meter failure
SOME LOAD STEPS
CANNOT BE ENERGIZED
1. Inoperative load step switches
2. Inoperative load step contactors