Unit installation
LON – Network 3065
Page 30
LPI-10 (Version: Compact)
Input quantities
Nominal input voltage
U
E
AC 120 / 230V
Input voltage range AC 85 to 264V
Nominal frequency
range
50/60Hz, 47 to 63Hz
Power failure buffering
> 50 ms at U
E
=195V
Nominal input current
I
E
0.8 / 0.5A
Making current
impulse
≤30mA
Efficiency η ≥ 75% in operation at nominal
value at 230 V AC
Recommended
circuit breaker
(IEC898) in the power
supply lead
from 6A Char. D
from 10A Char. C
from 16A Char. B
Output quantities
Nominal output voltage
U
A
DC 41.5 V ±2%
Residual ripple < 100mV
ss
at 10kHz < f < 200KHz
Spikes
(switching peaks)
< 200mV
ss
at 200KHz < f < 1MHz
Nominal output
current I
A
1A at U
E
85 to 195V
1.3A (1.5A max. permitted continuous
current from U
E
195V
Overload protection
typically at
1.6A; continuous short-circuit-proof with
pulsating restart attempt
Overvoltage protection
typically at
54 V
Start and restart time 5s < t < 10s
Environmental Conditions
During
transport/storage
-40° C to +70° C (-40° F to +158° F)
During operation 0° C to +40° C (32° F to +104° F)
Rel. air humidity 5 to 95%, w/o moisture condensation
Security
Degree of protection to
EN 60529
IP20