Owner`s manual
Electrical 9
Connection Procedure:
1. Connect the ground wire first as shown in Figure 11. The ground wire
must be a solid copper wire at least as large as the power supply wires.
2. There must be a solid metal connection between the pressure switch
and the motor for motor grounding protection. If the pressure switch is
not connected to the motor, connect the green ground screw in the
switch to the green ground screw under the motor end cover. Use a
solid copper wire at least as large as the power supply wires.
3. Connect the ground wire to a grounded lead in a service panel, to a
metal underground water pipe, to a metal well casing at least ten feet
(3M) long, or to a ground electrode provided by the power company or
the hydro authority.
4. Connect the power supply wires to the pressure switch as shown in
Figure 11.
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
Wiring Chart – Recommended Wire and Fuse Sizes
Branch Distance in Feet (Meters);
Max Fuse Wire Size AWG (mm
2
)
Load Rating 0-100 101-200 201-300 301-400 401-500
Model HP Amps Amps (0-30) (31-61) (62-91) (92-122) (123-152)
115 Volts:
2805E-01 1/2 9.9 15 14(2) 12(3) 10(5.5) 8(8.4) 8(8.4)
2806E-01 1/2 9.9 20 12(3) 10(5.5) 8(8.4) 6(14) 6(14)
2810E-01 3/4 12.4 20 12(3) 10(5.5) 8(8.4) 6(14) 6(14)
2815E-01 1 14.8 20 12(3) 8(8.4) 6(14) 6(14) 4(21)
230 Volts:
2805E-01 1/2 4.95 15 14(2) 14(2) 14(2) 14(2) 12(3)
2806E-01 1/2 4.95 15 14(2) 14(2) 14(2) 12(3) 12(3)
2810E-01 3/4 6.2 15 14(2) 14(2) 14(2) 12(3) 12(3)
2815E-01 1 7.4 15 14(2) 14(2) 14(2) 12(3) 10(5.5)