User Instructions
Document Type: Test Procedure
Equipment Name: Innovatec C and I Electric
Author: Dithien V. Ho, RF Design Engineer.
Page 8 of 24
3.2. NCTT Setting:
Using the PC, start the NCTT program.
Connect the FSU (Field Service Unit) with version 2 communications IC (Siliconians) to the PC.
Select “Setting” ! “Option”:
Serial Port: = Select appropriate Serial Port
Wakeup Interval = 1.25 Sec
Transmit Power = 28 dBm
Repeat Interval = 3 Sec (Min.); Unchecked “Random”
NCI Interaction = Checked “Automatic”
Conversion Factor = 0.00001
FIGURE 1
Select “O.K.”, then setting NCTT for C&I Electric Communications: