32A/40A  48A 80A
L1 (Black) 8 AWG  6 AWG  3 AWG
L2 (Red) 8 AWG  6 AWG  3 AWG
Ground 
(Green)
8 AWG (THHN)  8 AWG (THHN)  6 AWG (THHN)
6.  Turn on the circuit breaker that supplies power to the NEMA 14-50 outlet, NEMA 6-50 
outlet, or hardwired electrical connection.
Load Balancing
 > Load balance to Circuit only.
 > Load balance to panel is NOT recommended.
NOTE
Balancing to the panel or location can be done on a system that would otherwise 
work safely on its own. This can reduce usage during peak hours, saving cost to both 
the user and the owner of the stations.
 > Can only balance stations with the same specications.
 > Balancing  specications  cannot  exceed  the  rated  continuous  load  of  the  circuit.  (50 
amp circuit = 40 amp continuous load allowed) (NEC 625.41 & 42) 2017 code.
 > Per NEC 625.42 additional outlets per circuit can be added due to the JuiceNet Automated 
Load Management System.
 > Recommend no more than 3 per circuit. The maximum number of stations per circuit is 
determined by dividing the number of continuous load amps allowed based on circuit 
size by 8. (e.g. 40 amps / 8 amps = 5 stations maximum). Note this may result in a slower 
charge per car.