PN 52612:A ECN 05-276 Device Compatibility Document Document 52612 9/13/05 Rev: A
Table of Contents Control Panel Circuit Specifications - - - - - - - Compatible Two-Wire Smoke Detectors (UL Listed) Various Manufacturers - - - - - - - - - - - Maximum Number of Detectors per Zone - - - - System Sensor - - - - - - - - - - - - - - - Four-Wire Smoke Detectors/Devices (UL Listed) Notification Appliances (UL Listed) - - - - - - - • System Sensor - 24VDC - - - - - - - - - - • Gentex - 24VDC - - - - - - - - - - - - - - • Wheelock - 24VDC - - - - - - - - - - - - - Door Holders (UL Listed) - - - -
Control Panel Circuit Specifications Control Panel Circuit Specifications SK-2/SK-2E, SK-4/SK-4E Initiating Device Circuit Voltage: 17.3 - 24.6 Max Detector Circuit Standby Current: 2.
Compatible Two-Wire Smoke Detectors (UL Listed) Various Manufacturers Compatible Two-Wire Smoke Detectors (UL Listed) Various Manufacturers Detector ID Detector Type Base Model Base ID Standby Current (uA) System Sensor 2W-B A Photoelectric I3 N/A N/A 120 System Sensor 2WT-B A Photoelectric I3 N/A N/A 120 System Sensor 1100/D A Ionization N/A N/A 100 System Sensor 1151 A Ion B401 / B110LP / B116LP A 120 System Sensor 1400 A Ion N/A N/A 100 System Sensor 1451 A Ion B40
Maximum Number of Detectors per Zone System Sensor Maximum Number of Detectors per Zone When using two-wire smoke detectors containing supplementary relays or indicators, the operation of more than one detector per zone cannot be ensured System Sensor Base Model Model Number Device Compatibility Document PN 52612:A 9/13/05 MS-2 MS-4 2W-B N/A 16 2WT-B N/A 16 1100/D N/A 20 1151 B401/B110LP/ B116LP 1400 N/A 1451 B401B / B406B 1451DH DH-400 1800 N/A N/A 1851B B101B N/A 1851B B107B
Four-Wire Smoke Detectors/Devices (UL Listed) System Sensor Four-Wire Smoke Detectors/Devices (UL Listed) Detector Type Max Standby Current (mA) Alarm Current (mA) Gentex 8241 Ionization Photoelectric Photoelectric Base Photoelectric 0.10 0.10 0.10 * 0.50 * * * * * Gentex 824T1 Photoelectric 0.50 * Gentex 824CP1 Photoelectric 0.50 * Gentex 824CPT1 Photoelectric 0.50 * Hochiki HSC-4R1 Base * * Projected Beam 0.
System Sensor Four-Wire Smoke Detectors/Devices (UL Listed) Max Standby Current (mA) Alarm Current (mA) I3 Photo w/ IsolatedTherm/ Sounder/Relay .05 50 System Sensor 2W-MOD2 I3 Loop Test/Maintence Mod. .05 * System Sensor RRS-MOD I3 Reversing Relay/Sync Module Projected Beam .05 * 10 28.4 Projected Beam 17 38.
Notification Appliances (UL Listed) System Sensor - 24VDC Notification Appliances (UL Listed) Control panels with Notification circuits supplied by Special Purpose (FWR, Filtered) power must use appliances listed in this table. • • Refer to manufacturer’s installation instructions for more information. Contact manufacturer for current draws or additional options System Sensor - 24VDC Use only 24VDC devices with 24 volt control panels.
Notification Appliances (UL Listed) Gentex - 24VDC Gentex - 24VDC Use only 24VDC devices with 24 volt control panels.
Notification Appliances (UL Listed) Wheelock - 24VDC MODEL NUMBER & NOMENCLATURE (Wheelock) CH-CF1-IS-24-CFW, CH-CF1-LS-24-CFW, CH-CF1-MS-24-CFW Chime CH-DF1-IS-24-VFR, CH-DF1-LS-24-VFR, CH-DF1-LSM-24-VFR, CH-DF1-MS-24-VFR Chime CH70-24, CH90-24 Chime CH70-2415W, CH70-2430, CH70-2475, CH70-241575 Chime with Strobe CH70-24MCW-FR Multi-Candela Appliance CH90-2475C, CH90-24100C Chime with Strobe DSM-12/24 Dual Synchronization Module EH-DL1-WM-24-VF-R, EH-EL1-WM-24-VF-R Electronic Horn Strobes HSW-24-HFR, HSP
Wheelock - 24VDC Notification Appliances (UL Listed) MODEL NUMBER & NOMENCLATURE (Wheelock) SR-2415, SR-241575 Synchronized Strobe WMT-24-FR, WM1T-24-FR, WM3T-24-FR Strobes AS-24MCC-FW, CH90-24-MCC-FW, E90-24MCC-FW, ET90-24MCC-FW, HS-24-R/W, MIZ-24S-R/W, RSS-24MCC-FW Device Compatibility Document PN 52612:A 9/13/05 11
Door Holders (UL Listed) Wheelock - 24VDC Door Holders (UL Listed) MANUFACTURER MODEL Current (mA) TYPE Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM-980 Floor Mount, single 68 Rixon Firemark FM-996 Surface Wiring 68 Rixon Firemark FM-998 Concealed Wiring 68 Relays (UL Listed) MANUFACTURER 12 MODEL Current (mA) Air Products & Controls, LTD MR-101/C MR-201/C PAM-1 PAM-2 PAM-SD 15 35 15 15 15 System Sensor A7
Notes Device Compatibility Document PN 52612:A 9/13/05 13
Notes 14 Device Compatibility Document PN 52612:A 9/13/05
Notes Device Compatibility Document PN 52612:A 9/13/05 15
Notes 16 Device Compatibility Document PN 52612:A 9/13/05