User guide

IP Communicator Series Installation Document — P/N 53109:I 4/26/2010 7
Wiring the IPDACT Series Within the Fire Alarm Control Panel Enclosure
Figure 5 and Figure 6 detail the connections that must be made between the IPDACT Series and the FACP.
RJ45 Connector for connection to RS232 serial port.
Use a Serial to USB converter if the computer does not have an RS232 port.
(FOR PROGRAMMING USE ONLY)
Supplied Phone Cable
Supplied Phone Cable
(factory
installed)
Ferrite* Ferrite*
(minimum wire
gauge 22-14 Awg)
(Note the the male plug connectors on the other end of the Supplied Phone
Cable, plug into the Primary and Secondary Phone Jacks on the FACP DACT.)
1KΩ ELR
From FACP Nonresettable 24VDC (-)
From FACP Nonresettable 24VDC (+)
(minimum wire gauge 18-14 Awg)
RJ45 Connector for connection to
Ethernet/Internet (minimum wire
gauge 24-22 Awg)
* Refer to Figure 7 for Ferrite Bead Installation
.
The smaller ferrite bead is used on the “TO AP
connection.
The larger ferrite bead is used on the “24VDC”
connection.
Figure 5 IPDACT Wiring
ipdactbrd.wmf