User guide

4 IP Communicator Series Installation Document — P/N 53109:I 4/26/2010
2.1 Mounting IPDACT Series in the Fire Alarm Control Panel Enclosure
Install the IPDACT Series in the FACP backbox using the IPBRKT bracket or the IPCHSKIT, as described below.
2.1.1 IPBRKT Bracket Installation
1. Position the two tabs in the IPBRKT bracket over the two embossed protrusions in lower left corner of the backbox
and slide the bracket down with tabs going under embossed protrusions as illustrated in Figure 1.
IFC-400
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
IFC-200(E)
1
IPENC Enclosure
Section 2.2 on page 10
Unimode 640
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
ADT-NCA
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
Unimode 300/400
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
Unimode 2020/1010
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
IQ-636X(E)
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
ANSUL-NCA
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
IQ-396X
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
IQ-301(E)
1
IPENC Enclosure
Section 2.2 on page 10
MICRO-640I(E)
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
MICRO-NCA
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
MICRO-300I/400I
1
FACP Enclosure (IPCHSKIT)
2
Section 2.1.2 on page 6
MICRO-200I
1
IPENC Enclosure
Section 2.2 on page 10
1 Use of the UDACT Universal Digital Alarm Communicator/Transmitter is required for this
application. (For more information, see the UDACT Manual #50050.) This panel is only
compatible with the IPDACT-2 model.
2 If the system configuration does not support installation of the IPCHSKIT, use the IPENC enclosure.
Application (Power Source) Mounting Location Refer to Mounting Instruction Section
Table 2 IPDACT Series Mounting/Wiring Options for Retrofit Applications
Figure 1 IPBRKT Installation
Backbox
tab
backbox
embossed
protrusion
IPBRKT bracket
tab
backbox
embossed
protrusion
IPBRKTinstall1a.wmf