User guide

IP Communicator Series Installation Document — P/N 53109:I 4/26/2010 15
FACP
Main Circuit Board
FACP Backbox
AC Power*
HP300ULX Power Supply Enclosure
RJ45
Ethernet/
Internet
Connection
Primary
Phone Line
Secondary
Phone Line
* The FACP and HP300ULX Power Supply must be connected to the same AC main circuit.
This will allow the FACP to transmit an AC fail signal upon AC loss for both panels.
Figure 15 Wiring IPDACT-2 and IPDACT-2UD to HP300ULX and FACP
IPDACT-2UDHP300ULXitoFACP90x2a.wmf
metal conduit (6” max.
when using the supplied
phone cables). Longer
distances (up to 20’ within
the same room) is
acceptable when
supplemental phone cables
are used.