MODEL 5895XL Intelligent Power Module for the 5820XL System Installation and Operations Manual ECN: 1 -0317 Document 151142 Rev: H 151142:H
Content Section 1 Overview ...................................................................................................................................................... 1-1 1.1 5895XL Description ................................................................................................................................. 1-1 1.1.1 Maximum Number of SBUS Modules ............................................................................................. 1-2 1.2 Agency Requirements ...........
Model 5895XL Intelligent Power Module Installation and Operation Manual 3.5.4 Installing 2-Wire Smoke Detectors ................................................................................................. 3-10 Class B Installation ...................................................................................................................... 3-10 2-Wire Class A Smoke Detector Installation .............................................................................. 3-11 3.5.
Section 1 Overview 1.1 5895XL Description The Model 5895XL Intelligent Power Module provides additional power and circuits to the IntelliKnight 5820XL FACPs. The 5895XL can power all IntelliKnight compatible modules, including SLC devices (via a Model 5815XL SLC Expander), remote annunciators (Model 5860); notification appliances, auxiliary power modules, and all other compatible modules. Note: The 5808 does not use 5815XL SLC expanders. The 5895XL has six Flexputs™ and two programmable relays.
Model 5895XL Intelligent Power Module Installation and Operation Manual 1.1.1 Maximum Number of SBUS Modules The chart below shows the maximum number of compatible modules that can be used in an IntelliKnight installation. Modules can be distributed among the main panel SBUS and each additional 5895XL SBUS in virtually any combination.
Overview Figure 1-1 Example 5895XL Installation Overview 151142 1-3
Model 5895XL Intelligent Power Module Installation and Operation Manual Figure 1-2 Example 5895XL Installation Overview (Details Added) 1-4 151142
Overview 1.2 Agency Requirements The 5895XL has the same requirements as the main control panel. These requirements are listed in the IntelliKnight 5820XL Installation Manual (P/N 151209). 1.3 About This Manual This manual covers installation of 5895XL hardware. Software configuration information is contained in the IntelliKnight 5820XL Installation Manual (P/N 151209). 1.
Model 5895XL Intelligent Power Module Installation and Operation Manual 1-6 151142
Section 2 Before You Begin Installing 2.1 What’s in the Box? The Model 5895XL ships with the following hardware: • A cabinet with all hardware assembled • Two keys for the front door • Ten 4.7K ohm end-of-line resistors Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used. • A battery cable for batteries wired in series 2.2 Environmental Specifications It is important to protect the 5895XL control panel from water.
Model 5895XL Intelligent Power Module Installation and Operation Manual 2.4 5895XL Board and Terminal Strip Description Figure 2-1 shows the 5895XL circuit board including location of terminals, the DIP switch for setting module ID, and the LED.
Before You Begin Installing Table 2-1: Terminal Strip Description and Electrical Ratings Terminal # and Label Rating Description Voltage 1 L AC input (hot) 2 G Earth ground 3 N AC input (neutral) 4 5 6 7 8 X O X O X 9 O 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 X O X O X O B A + B A + N.C. C N.O. N.C. C N.O. B 31 A 32 33 + - 120/240 VAC, 50/60 Hz N/A 120/240 VAC, 50/60 Hz Current 2.7 A 1.4 A N/A 2.7 A 1.4 A 3.0 A Notification Circuits 100 mA Initiation Circuits 3.
Model 5895XL Intelligent Power Module Installation and Operation Manual 2.5 Earth Fault Resistance Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP.
Before You Begin Installing 2.6 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 2.6.1 Worksheet Requirements The following steps must be taken when determining 5895XL current draw and standby battery requirements. Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2) 1. For the 5895XL, the worst case current draw is listed for the panel, addressable devices, and SLC expanders.
Model 5895XL Intelligent Power Module Installation and Operation Manual 2.6.2 Current Draw Worksheet For *each 5895XL in the installation, use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.
Before You Begin Installing 2.7 2.7.1 Wiring Specifications Length Limitations This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B). 2.7.2 Calculating Wiring distance for SBUS modules The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with SBUS accessory modules.
Model 5895XL Intelligent Power Module Installation and Operation Manual These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below). Table 2-5: Wire Distances Per Wire Gauge Wiring Distance: SBUS Modules to Panel Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft. 0.200 926 ft. 2344 ft.
Before You Begin Installing Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface The total worst case current is calculated as follows: 5860 Current Draw = 2 x .100 amps = .200 amps 5895XL Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .200 amps 5824 Current Draw = 1 x .040 amps = .
Model 5895XL Intelligent Power Module Installation and Operation Manual 2.7.3 Wire Routing You must follow power-limited wiring techniques, which includes maintaining one-quarter inch spacing between power-limited and nonpower-limited circuits and separating high and low voltage circuits.
Section 3 Hardware Installation 5895XL installation involves the following steps: • AC power (Section 3.1) and backup battery connection (Section 3.2). • Physical connection to the IntelliKnight 5820XL FACP or to the controlling 5895XL (see Section 3.3). • Setting an ID for the 5895XL (Section 3.3.1). • Physical connection of SBUS modules that will be powered by this 5895XL (Section 3.4).
Model 5895XL Intelligent Power Module Installation and Operation Manual 3.2 Battery Connection The 5895XL battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section Table 2-4). Note: When your backup batteries requirements use backup batteries that are to large to fit into the 5895XL cabinet. The AB-33 cabinet holds batteries up to the 33 AH size.
Hardware Installation 3.3 Connecting the 5895XL to the FACP 1. Connect the 5895XL to the appropriate SBUS. The 5895XL can be connected directly to the IntelliKnight 5820XL FACP or can be daisy-chained to another 5895XL. Figure 3-3 and Figure 3-4 show both connections. 2. Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2-1 shows the location of the DIP switches on the 5895XL board. 3. Configure the 5895XL module by adding it to the system (through JumpStart or manually).
Model 5895XL Intelligent Power Module Installation and Operation Manual See Figure 3-6 for SBUS Module Connections See Figure 3-6 for SBUS Module Connections Figure 3-4 Class A 5895XL Connection to FACP 3-4 151142
Hardware Installation 3.3.1 Setting the Device ID board to set the module ID#. Figure 2-1 shows the location of the DIP switch on the board.
Model 5895XL Intelligent Power Module Installation and Operation Manual 3.4 Connecting SBUS Modules to the 5895XL 1. Connect SBUS modules to the 5895XL as shown in Figure 3-6 or Figure 3-7. 2. All SBUS modules must have an ID. Use the DIP switches on the module board to assign an ID number (1-31) to the module. This number identifies the module to the 5895XL and must be unique. 3. Software configuration steps vary for each SBUS module.
Hardware Installation 3.5 Flexputs™ I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the 5895XL panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder). This section of the manual explains how to install conventional notification appliances and initiating devices to be used with the 5895XL. 3.5.
Model 5895XL Intelligent Power Module Installation and Operation Manual 3.5.2.2 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as shown in Figure 3-9. 2. Configure the circuit for Class A in programming (see Section 7.4 of the Installation Manual P/N 151209).
Hardware Installation 3.5.3 Conventional Initiation Circuits This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations. 3.5.3.1 Class B Inputs You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel. To install a Class B switch: 1. Wire the Class B switch as shown in Figure 3-10. 2.
Model 5895XL Intelligent Power Module Installation and Operation Manual 2. Configure the circuit through programming (see Section 7.4 of the Installation Manual 151209). Note: I/O circuit 5 and 6 used as an example. Any I/O point pairing could be used. Figure 3-11 Class A initiating Switches Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used.
Hardware Installation 2-Wire Class A Smoke Detector Installation To install a Class A two-wire smoke detector, wire as shown in Figure 3-13. Note: I/O circuit 5 and 6 used as an example. Any I/O point pairing could be used. Figure 3-13 Two-Wire Class A Smoke Detector Connections Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used.
Model 5895XL Intelligent Power Module Installation and Operation Manual 3.5.5 Installing 4-Wire Smoke Detectors Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed four-wire detector to the control panel. Installing a Class B 4-Wire Smoke Detector Figure 3-14 illustrates how to install a 4-wire Class B smoke detector.
Hardware Installation Installing 4-Wire Class A Smoke Detectors Figure 3-15 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once. 2. Smoke power is supplied to each Class A loop as shown in Figure 3-15.
Model 5895XL Intelligent Power Module Installation and Operation Manual 2. Configure the auxiliary power output through programming for Door Holder, Constant or Resettable power. Figure 3-16 Flexput Circuits Used as Auxiliary Power 3.5.6.1 Door Holder Power Door holder is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 24-volt power present at their terminals. Any alarm will cause power to discontinue.
Appendix A Compatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the 5895XL must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Faraday A-2 Model Audio Visual Type 446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M.
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Faraday con’t 151142 Model Audio Visual Type 5510 Strobe 5511 Strobe 5512 Strobe 5516 Strobe 5517 Strobe 5518 Strobe 5519 Strobe 5521 4” Square Sync Strobe 5522 4” Square Sync Strobe 6120 Horn 6140 Horn 6223 Horn 6226 Horn/Strobe 6227 Horn/Strobe 6228 Horn/Strobe 6243 Electron-Mechanical Horn 6244 Electron-Mechanical Horn 6245 Electron-Mechanical Horn 6246 Electron-Mechanical Horn/Strobe
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer FCI FCI Federal Signal A-4 Model Audio Visual Type S2415-FC Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/S
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual GEC-24-15 Horn/Strobes GEC-24-30 Horn/Strobes GEC-24-60 Horn/Strobes GEC-24-75 Horn/Strobes GEC-24-177 Horn/Strobes GEC-24-110 Horn/Strobe GEC-24-15/75 Horn/Strobe GX91 MiniHorn Steady Tone GX93 MiniHorn Temporal Tone HG124 Gentex Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75 Horn/S
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Visual Type CHR Chime CHW Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe HR Horn HW Horn HRK Horn P2R 2-Wire Horn/Strobe P2R-P 2-Wire Horn/Strobe PC2R 2-Wire Horn/Strobe PC2R-P 2-Wire Horn/Strobe P2RH 2-Wire Horn/Strobe High Candela P2RH-P 2-Wire Horn/Strobe High Candel
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual PC4W 4-Wire Horn/Strobe P4WH 4-Wire Horn/Strobe High Candela PC4WH 4-Wire Horn/Strobe High Candela P4RK 4-Wire Horn/Strobe PC4RK 4-Wire Horn/Strobe P4RHK 4-Wire Horn/Strobe High Candela PC4RHK 4-Wire Horn/Strobe High Candela PC4RH 4-Wire Horn/Strobe High Candela SR Strobe SR-P Strobe SCR Strobe SCR-P Strobe SRH Strobe Hi
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio 4 Horn AH-24 Horn AH-12WP Horn Weatherproof AH-24WP AMT-241575W Horn Weatherproof Multi-Tone Horn Strobe Mutli-Tone Horn Strobe Multi-Tone Horn Strobe AMT-241575W-NYC AMT-12/24 Multi-tone Horn AMT-12/24 NYC Multi-tone Horn AS-121575W A-8 Type AH-12 AMT-24MCW Wheelock Visual Horn/Strobe NH-12/24 AS-241575W
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio CH90-24MCCH Chime/Strobe HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MultitoneHorn Strobe Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MT-241575W Horn Multitone Horn Strobe MTG-121575W Multitone Horn Strobe MTR-121575W
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Wheelock con’t A-10 Model Audio Visual Type RSS-121575W Strobe RSS-241575W Strobe RSS-24MCC Strobe RSS-24MCCR Strobe RSS-24MCCH Strobe RSS-24MCCHR Strobe RSS-24MCW Strobe RSS-24MCWH Strobe RSSP-121575W Strobe RSSP-241575W Strobe RSSR-2415W Strobe RSSR-2415C Strobe RSSR-2475W Strobe RSSR-2475C Strobe RS
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Wheelock con’t Model Audio Type RSSWP-24MCWH Strobe Weatherproof ZRS-MCWH Strobe ZRS-24MCC Strobe ZRS-24MCCH Strobe MB-G6-24 Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell MB-G10-12 Motor Bell MIZ-24-R Mini-Horn MT-12/24-R Multitone Horn MT4-12/24 Multitone Horn Strobe Multitone Horn Strobe ZRS-MCW 151142 Visual MTWPR-24MCCH NH-12/24R Horn HSR Horn/St
Model 5895XL Intelligent Power Module Installation and Operation Manual A.2 Door Holder Device The following UL listed door holder can be used with the 5895XL: ESL DHS-1224 A.3 Two-Wire Smoke Detectors Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. 5895XL Identifier Operating Voltage Range 24H 18.5–27.
Compatible Devices Table A-2: Compatible Two-Wire Smoke Detectors Manufacturer Detection Systems Model Name or Number (Base model name or number in parentheses.
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-2: Compatible Two-Wire Smoke Detectors Manufacturer Falcon Faraday Model Name or Number (Base model name or number in parentheses.
Compatible Devices Table A-2: Compatible Two-Wire Smoke Detectors Manufacturer System Sensor (cont.) Model Name or Number (Base model name or number in parentheses.
Model 5895XL Intelligent Power Module Installation and Operation Manual A-16 151142
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. • This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposer to adverse environmental conditions, or have been modified in any manner whatsoever.
or call Silent Knight at 203-484-7161 to obtain a RMA (Return Authorization) number and request advanced replacement, • A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Silent Knight. All returned products must comply with the guidelines described under “General Terms and Conditions”.
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.