Instruction Manual
Normal Operation
150805 19
4.1.3 5230 Key Functions
The 5230 annunciator function keys are described below. Keys not described here are used only for entering
digits.
Note: The message “TRY AGAIN” appears if you do not press any keys for five seconds while accessing a function or
if you attempt to access a function before exiting from another function.
4.2 Operating Modes
Table 4-1: Key Functions
FUNCTION NAME EXPLANATION KEYSTROKES
CLEAR Corrects mistakes. If you enter a function
incorrectly, the 5230 will emit a long, high-
pitched tone.
SYSTEM TEST Tests the communicator by sending a test
report to the central station.
[Installer’s or Operator’s Code]
RESET DIALER Aborts an in-progress call to the central
station.
[Installer’s
Code]
BEGIN DOWNLOAD Begin downloading session.
[Installer’s Code]
ENTER PROGRAMMING
MODE
Enters programming mode where you
change programmable options.
[Installer’s Code]
To exit programming mode, press
SET TIME To set the time:
1. Press
2. Enter Installer’s or Operator’s Code. The SET MODE LED will turn on.
3. Enter the time in 24-hour military format (include leading zeros).
EXAMPLE:
To enter SET TIME mode and set the time for 3:30 PM, the keystrokes are:
[Code] .
OPERATING MODE: ALLOWED DURING ALARM: CODE REQUIRED:
0 System test NO Installer’s or Operator’s
3 Dialer reset YES Installer’s
4 Download NO Installer’s
9 Set time NO Installer’s or Operator’s
27 Program NO Installer’s
CLEAR
0 ENTER
3 ENTER
4 ENTER
2 7 ENTER
STEP STEP CLEAR CLEAR
9 ENTER
9 ENTER 1 5 3 0 ENTER