User Guide

Cut Along the Dotted Line
SK-5208 Basic Operating Instructions P/N 151214 Rev. A
These instructions must be framed and displayed next to the panel in accordance with NFPA
72 fire code for Local Fire Alarm System.
How To
Do This
Comments
Press Display Message Press
Test the system
Enter Code
The system will perform a display lamp test and a
communication test.
Reset Alarms
Enter Code Resets system.
Reset the Dialer
Enter Code Resets the dialer and aborts the call to central station.
Display History
Events
Enter Code
Displays the panel history, which includes alarms,
supervisories, troubles, reports, time and date changes, etc.
Show Status
Enter Code
View existing system status. List Alarms first,
supervisories and then troubles.
Silence Troubles or
Alarms
or
Enter Code
Disable/Enable a Zone
Zone # +
Enter Code Repeat the process to enable the zone.
Disable/Enable NAC
NAC # +
Enter Code
Repeat the process to enable the NAC.
Conduct a Fire Drill
Enter Code
To End the Fire Drill press then code.
Reset Detectors
Enter Code Resets all smoke detector power.
Walk Test the System
Enter Code
To End the Walk Test press .
Menu of Options
Press or
to scroll trough list.
Enter Installer
Code
To exit press or wait 15 seconds.
Acknowledge Events
Events can be acknowledged by pressing the button. No code is required to acknowledge events. The status LEDs
(Alarm, Supervisory and Trouble) will flash when an un-acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble LED) stop flashing and turn on
steady. When viewing system status the LCD displays “Acked” for each individual event once it has been acknowledged. The
control panel piezo will silence after all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been
acknowledged. Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the history buffer will be
preceded with an asterisk “*”.
LEDs Meaning
LED Status Condition
ALARM (red)
Off Normal condition
On System in alarm.
Flashing LED will flash when a alarm condition exists that has not been acknowledged.
SUPERVISORY (yellow)
Off Normal condition
On If a supervisory condition exist on the system.
Flashing LED will flash when a supervisory condition exists that has not been acknowledged.
TROUBLE (yellow)
Off Normal condition
On Trouble condition exists
Flashing LED will flash when a trouble condition exists that has not been acknowledged.
SILENCED (yellow)
Off Normal condition.
On Alarm or trouble condition has been silenced but condition still exists.
AC (green)
On Panel is running on AC (normal condition); standby battery fully charged.
Off Panel has lost all power.
Flashing Panel is running on battery power only or AC power only.
0
1
3
5
6
7
1 0
2 0
2 1
2 2
For Service Contact:

Summary of content (1 pages)