Specifications
Model SK-5208 Installation Manual 151204
6-5
6.2.1 Default Settings for 3/1 Format
Table 6-3 displays the default settings which are set in the Misc. Reporting section of Programming.
Table 6-3: Default Settings for 3/1 Format
Programming
Option
Menu Item Choices Default Comments
Misc Reporting
Test Time 00:00 - 23:59 12:00
Selects the time of day the control will send an
automatic test signal to a central station
receiver.
Test Interval
Every 4 Selects the period to which the system
performs an Automatic Self Test, keyed off the
Test Time.
Every 6
Every 12
Every 24 X
AC Delay 0-30 Hours 2
Selects the delay time (in hours) before the
control will report an AC power loss to the
central station.
Report Walk Test
No X
No zone information will be reported just test
begin and test end.
By Zone
Test begin, test end, and all events in between
will be reported to central station.
*3/1 Alarm
0 - 9
* Event code for 3/1
and 4/2 reporting
formats.
0
Alarms for Fire, Waterflow, Undefined, Heat,
Cold, and Water events.
*3/1 Alarm Rst 2
Alarms restores for Fire, Waterflow,
Undefined, Heat, Cold, and Water events.
*3/1 Supervisory 6 Sprinkler supervisories.
*3/1 Restore 7
Restore reports for Troubles, Supervisories,
and unbypasses. The only exceptions are the
restores listed as alarm restores.
*3/1 Trouble 8
All system and zone troubles, and zone/NAC
bypasses, and NACs troubles.
*3/1 Test 9 All test events.