6.2 Reporting Codes
Table 6-2 list the events sent by the SK-5208 and the code that is sent for that event by the type of reporting
format used.
Note: Codes under in the SK4/2 and 3/1 1400 & 2300 column are the codes programmed for 3/1 reporting for-
mats in Misc Reporting. See Section 4.2.10 for Misc. Reporting options and Table 6-3 for default 3/1 format
reporting values.
Table 6-2: Event and Reporting Code by Format
Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID
AC Trouble AT0 T0 Trouble Code 1 301 000
AC Restore AR0 R0 Restore Code 3 301 000
Annunciator Trouble 1-7 ET17 - ET23 T7 - T3 Trouble Code 1 330 017 - 1 330 023
Annunciator Restore 1-7 ER17 - ER23 R7 - R3 Restore Code 3 330 017 - 3 330 023
Bell Trouble 1-4 ET32-ET35 T2 - T5 Trouble Code 1 330 032 - 1 330 035
Bell Restore 1-4 ER32-ET35 R2 - R5 Restore Code 3 330 032 - 3 330 035
Smoke (Loop) Power Trouble ET36 T6 Trouble Code 1 320 036
Smoke (Loop) Power Restore ET36 R6 Restore Code 3 320 036
Aux Power Trouble ET37 T7 Trouble Code 1 330 037
Aux Power Restore ER37 R7 Restore Code 3 330 037
Earth Ground Trouble ET38 T8 Trouble Code 1 330 038
Earth Ground Restore ER38 R8 Restore Code 3 330 038
Keypad Power Trouble ET40 T0 Trouble Code 1 330 040
Keypad Power Restore ET40 R0 Restore Code 3 330 040
5217 Expander Trouble ET51-ET52 T1 - T2 Trouble Code 1 330 051 - 1 330 052
5217 Expander Restore ER51-ER52 R1 - R2 Restore Code 3 330 051 - 3 330 052
5280 Expander Trouble ET61-ET68 T1 - T8 Trouble Code 1-330 061 - 1 330 068
5280 Expander Restore ER61-ER68 R1 - R8 Restore Code 3-330 061 - 3 330 068
NAC Bypass ET101-ET104 T1 - T4 Trouble Code 1-330 101 - 1 330 104
NAC Restore ER101-ER104 R1 - R4 Restore Code 3-330 101 - 3 330 104
NAC Supervisory (See Note) SS101-SS104 S1 - S4 Supervisory Code 1 203 101 - 1 203 104
NAC Supervisory Restore (See Note) SR101-SR104 R1 - R4 Restore Code 3 203 101 - 3 203 104
Fire Alarm 1-30 FA1 - FA30 A1 - A0 Alarm Code 1 110 001 - 1 110 030
Fire Bypass FB1-FB30 T1 - T0 Trouble Code 1 571 001 - 1 571 030
Fire Alarm Restore 1-30 FH1 - FH30 AR1 - AR0 Alarm Restore Code 3 110 001 - 3 110 030
Fire Test Begin FI1 - FI10 Test 0 Test Code 1 604 000
Fire Trouble Restore 1-30 FJ1 - FJ30 R1 - R0 Restore Code 3 373 001 - 3 373 030
Fire Test End FK0 Test 0 Test Code 1 604 000
Fire Restore/Clean-Me Restore FR1-FR30 R1 - R0 Restore Code 3 110 001 - 3 110 030
Note: These reports are sent for Notification Appliance Circuits that are programmed for releasing operation.