Specifications
Programming 151204
4-20
NAC Options Fire Drill NAC 1 2 3 4
All NACs
selected
If number is selected that NAC will activate during
a fire drill.
Relay Options
Silence Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay can be silenced for
Trouble and Supervisory conditions only. (This
includes relays programmed for AC Trbl.)
Fire Relay 1 _ _ _
Relay 1
selected
If a relay is selected, that relay will activate for fire
alarm conditions.
Prealarm Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
prealarm conditions.
Aux Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
Auxiliary conditions.
Waterflow Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
waterflow conditions.
Superv Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
supervisory conditions.
Crossalert A Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
crossalarm conditions.
Release A Relay _ _ _ _
No Relays
selected
If selected will activate for releasing group “A”.
Crossalert B Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
crossalarm conditions.
Release B Relay _ _ _ _
No Relays
selected
If selected will activate for releasing group “B”.
Trouble Relay _ _ _ 4 X
Relay will be activated when no troubles exist and
will deactivate when a trouble condition occurs.
Fire Drill Relay 1 _ _ _
Relay 1
selected
If a relay is selected, that relay will activate for fire
drills.
AC Trbl _ _ _ _
No Relays
selected
If a relay is selected, that relay will be activated
when AC is normal and will deactivate when a
Low AC condition exists.
User (1-10) #
Code
Code # Type
Installers
5208 and
123456
Operators 1111
Not Used
User # Code
Enter 3 to 6 digit
number
Enter any value from 001 to 999999.
Table 4-4: Programming Options
Programming
Option
Menu Item Choices Default Comments