Specifications
Model SK-5208 Installation Manual 151204
3-9
Remote Annunciator
Connections
30 SKI Used to connect 5235 remote annunciators to the control
panel.
31 SKO
32 PWR
33 GND
Notification Appliance
Circuit 4
34 +
NAC4
3 Amp maximum per circuit. Voltage 27.4 VDC, 1.5
Ohms Maximum.
Note: Total control panel current is 6 Amps.
35 _
Notification Appliance
Circuit 3
36 +
NAC3
37 _
Notification Appliance
Circuit 2
38 +
NAC2
39 _
Notification Appliance
Circuit 1
40 +
NAC1
41 _
Auxiliary Relay 4
42 NO Relay contacts are rated at 2.5 A, 24 VDC/24VAC
(inductive rating). 5A, 24 VDC/24 VAC (resistive).
Connect to power limited source only.
43 COM
44 NC
Auxiliary Relay 3
45 NO
46 COM
47 NC
Auxiliary Relay 2
48 NO
49 COM
50 NC
Auxiliary Relay 1
51 NO
52 COM
53 NC
Telco Line 2
54 TIP
P2
Telephone line 2 connection terminals (see Section 3.10
for wiring diagram).
55 RING
56 TIP
T2
57 RING
Telco Line 1
58 TIP
P1
Telephone line 1 connection terminals (see Section 3.10
for wiring diagram).
59 RING
60 TIP
T1
61 RING
Table 3-4: Terminal Descriptions
Function
Terminal
Number