Model SK-5208 Fire Control / Communicator Installation and Operations Manual Document 151204 05/15/2014 Rev: M P/N 151204:M ECN: 14-0068
Installation Procedure Adherence to the following will aid in problem-free installation with long-term reliability: Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing.
Contents Contents Section 1 Introduction .............................................................................................................................................. 1-1 1.1 1.2 1.3 Model SK-5208 Features ......................................................................................................................... 1-1 About This Manual ..................................................................................................................................
Installation Manual 3.14.2 Model SK-5235 Remote Annunciator ............................................................................................ 1-16 3.14.2.1 Mounting the SK-5235 Remote Annunciator ...................................................................... 1-16 3.14.2.2 Wiring the SK-5235 ............................................................................................................. 1-17 3.14.3 Model SK-5280 Status Display Module ..........................................
Contents 5.4 5.5 LED Indicators ......................................................................................................................................... 1-3 Releasing Operation ................................................................................................................................. 1-4 5.5.1 Cross Alarm Operation ..................................................................................................................... 1-4 5.5.1.
151204 Section 1 Introduction The Model SK-5208 is an 24-volt 10-zone fire alarm control panel (expandable up to 30 zones using SK-5217 Zone Expanders) with a digital communicator that meets NFPA 72 requirements. The SK-5208 cabinet can be surface mounted or semi-flush mounted. 1.
Model SK-5208 Installation Manual 1.3.1 151204 Optional Accessories Table 1-1: Compatible Modules Manufactured by Silent Knight Model What It Does SK-5217 Zone Expander Adds 10 zones to the SK-5208 for a total expansion of the system to 30 zones. SK-2190 Accessory Cabinet Used for remote mounting of the SK-5217 Zone Expander. Dimensions: 10-3/8”W x 10-3/16”H x 3”D (26.35 cm W x 25.88 cm H x 7.
Introduction 151204 fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. • Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances.
151204 Section 2 Agency Listings and Requirements Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to NFPA 72. 2.1 1.
Agency Listings and Requirements 2.2.1 151204 Requirements for All Installations General requirements are described below. The sections that follow describe additional requirements for the type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on). 1. Use UL listed smoke detectors compatible with the SK-5208. Refer to Appendix A. 2. Use UL listed compatible notification devices. Refer to Appendix A.
151204 Section 3 Control Panel Installation 3.1 Electrical Specifications Table 3-1: Electrical Specifications 3.2 Primary AC 120 Vrms at 60 Hz, 3A Total DC Load 6A Accessory Power 27.4 VDC, 1A Smoke Power 27.4 VDC, 1A Battery Charging Voltage 27.4 Battery Charging Current .75 A max. Class B (Style B) Circuit Current 95 mA max. Telephone Minimum Input Sensitivity 35 dB Good Phone Line Voltage 3V Maximum Low Battery Detect 20.4 Minimum Low AC Detect 98 Notification Power 3A max.
Control Panel Installation 151204 false alarms. Avoid pulling one multiconductor cable for the entire panel. Instead, separate the wiring as follows: 1/4" spacing must be maintained between each of these circuit types; as well as between power limited and non-power limited circuits.
Model SK-5208 Installation Manual 3.4 151204 Control Board Components Figure 3-2 is a wiring diagram for wiring the Model SK-5208 panel.
Control Panel Installation 3.5 151204 Mounting the SK-5208 Read the environmental specifications in section 3.2 on page 1 before mounting the SK-5208 panel. The SK-5208 cabinet dimensions are: 16" W x 26.4" H x 4" D (40.64 cm W x 67.06 cm H x 10.16 cm D). The SK-5208 panel should be located within a secured area, where it is accessible to main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles.
Model SK-5208 Installation Manual 3.6.2 151204 Current Draw Worksheet Use Table 3-2 to determine current requirements during alarm/battery standby operation. (Copy the page if additional space is required.) Table 3-2: Current Draw Calculations Device # of Devices For each device use this formula: This column SK-5208 Fire Panel (Current draw 1 from battery) Panel Accessories SK-5217 Zone Expander 5824 Serial/Parallel Interface Gateway Module (2 max.) (1 max.
Control Panel Installation 151204 10% of zones in alarm, but in no case less then three zones per UL864 3.6.3 Maximum Battery Standby Load Table 3-3 shows the maximum battery standby load for the SK-5208 based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2) must be less than the number shown in Table 3-3 for the battery size used and standby hours required.
Model SK-5208 Installation Manual 151204 Warning To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected before attempting to connect the Model SK-5208 control panel. Do NOT apply power to this panel until all accessories are properly connected. Note: Note: All conduit and wiring connected to the SK-5208 must meet the applicable National Electric Code, NFPA Standards, state, and local building code requirements.
Control Panel Installation 151204 Caution Apply AC power before connecting the batteries to the power supply to prevent arcing on battery terminals. Note: The total current draw on smoke power, accessory power, and notification device outputs must not exceed 6A. 3.9 Terminal Strip Description The terminal strips on the PC board are non-removable. Table 3-4 lists the functions of each terminal. See Section 3.4 for the board layout. Table 3-4: Terminal Descriptions Function Zone 1 input.
Model SK-5208 Installation Manual 151204 Table 3-4: Terminal Descriptions Function Remote Annunciator Connections Terminal Number Terminal Label 30 SKI 31 SKO 32 PWR 33 GND Notification Appliance Circuit 4 34 + 35 _ Notification Appliance Circuit 3 36 + 37 _ Notification Appliance Circuit 2 38 + 39 _ Notification Appliance Circuit 1 40 + 41 _ 42 NO 43 COM 44 NC Auxiliary Relay 4 Auxiliary Relay 3 Auxiliary Relay 2 Auxiliary Relay 1 Telco Line 2 Telco Line 1 45
Control Panel Installation 3.10 151204 Telephone Line Connection The SK-5208 connects to two separate telephone lines to report data to the central station. An RJ31X jack should be installed by the telephone company for each line. Figure 3-4 shows how to wire the telephone line interconnect cords (not provided) to the SK-5208. Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together with initiation or notification device wires.
Model SK-5208 Installation Manual 151204 zones. These zones must be wired using normally open contacts. Supervised Power Limited Figure 3-5 Class A (Style D) Supervised Fire Circuit Maximum voltage: Circuit Current: Maximum circuit Resistance: 3.11.2 17.5 to 28 VDC Full Wave Rectified 95 mA 50 ohms Class B (Style B) Zones Zones 3 through 10 are Class B (Style B) only fire zones. Zones 1 & 2 may also be programmed as Class A (Style D) or Class B (Style B), see Section 4.2.
Control Panel Installation 151204 Maximum circuit Resistance - 50 ohms Maximum Total alarm current for all Class B (Style B) zones - 1 A Maximum Standby Current per Zone:3.0 mA Maximum Alarm Current per Zone:95 mA 3.11.3 Four-Wire Smoke Detector Connection Figure 3-7 illustrates how UL listed four-wire smoke detectors must be connected to Class B (Style B) zones. When wiring a four-wire smoke detector to the Class B (Style B) zones, you must use a Power Supervision Unit, such as Silent Knight’s 160150.
Model SK-5208 Installation Manual 3.11.4 151204 Two-Wire Smoke Detector Connection Figure 3-8 shows how to connect two-wire smoke detectors to Class B (Style B) zones. Silent Knight SLK-24F 2-wire detector with HSB-224 base – – + +Supervised Power Limited 4.7 k UL Listed EOL Model 7628 Figure 3-8 Two-Wire Smoke Detector Wiring See Appendix A for a list of two-wire smoke detectors that may be used with the SK-5208. Note: Two-wire detectors can be configured for Enhanced Mode.
Control Panel Installation 151204 on each circuit. Figure 3-9 shows how to connect the notification circuits to the SK-5208. 3 Amps Max. per circuit full wave rectified, 27.5 VDC, 1.5 Ohms Maximum. Supervised Power Limited 4.7 k UL Listed EOL Model 7628 Figure 3-9 Supervised Notification Appliance Wiring 3 Amp maximum current draw from any single NAC output (not to exceed a total current draw of 6 amps for the control panel).
Model SK-5208 Installation Manual 151204 3.13 Auxiliary Relays The SK-5208 provides four programmable auxiliary relay outputs. Relays can be programmed to activate for the following conditions, either for all zones or by individual zone: pre-alarm (not acceptable for NFPA 72 Central Station), fire alarm, auxiliary alarm, alarm by zone, and system or circuit troubles (loss of AC, low battery, failed to communicate, phone line troubles, fire drills, and notification circuit troubles).
Control Panel Installation 151204 determine the dip switch positions for each possible ID code. Table 3-5: ID Dip Switch Settings Switches1 ID Number 1 2 3 4 02 Down Down Down Down 1 Up Down Down Down 2 Down Up Down Down 3 Up Up Down Down 4 Down Down Up Down 5 Up Down Up Down 6 Down Up Up Down 7 8 Not used3 1. Switch Settings: Up = On Down = Off 2. Not supervised. 3. ID number 7 and 8 are not valid ID settings. 3.14.
Model SK-5208 Installation Manual 151204 2. Secure it to the wall using #6 or #8 screws. The mounting plate should be oriented so that the word TOP is toward the top of the plate and facing you. A square hole is provided in the mounting plate to run the wiring to the annunciator. 3. When all of the wires have been connected to the annunciator, set the top of the annunciator over the tabs on the top of the mounting plate. Make sure the wires do not get pinched between the frame and the mounting plate.
Control Panel Installation 3.14.3 151204 Model SK-5280 Status Display Module The Model SK-5280 Status Display module provides outputs and control functions for remote annunciation of alarm, trouble, and supervisories for each zone.The system can supervise up to eight SK-5280 Status Display Modules. Note: The driver outputs are non-supervised. Relays must be connected to power limited sources only. 4 On-board Relays ID Number DIP Switch Relay Rating 2.
Model SK-5208 Installation Manual 151204 - 30, or system status outputs. See Section 4.2.11. 5280 Supervised Power Limited Class B Control Panel Figure 3-14 Model SK-5280 Connection to the Control Panel 3.14.3.1 Mounting the SK-5280 The SK-5280 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet. Mounting the SK-5280 into SK-5208 Cabinet Follow these steps to properly mount the SK-5280 into the SK-5208 cabinet: 1. Remove power from the control panel. 2.
Control Panel Installation 151204 3. Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14. 4. Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for information on setting ID numbers. 5. Reconnect power to the control panel. Mounting the SK-5280 into the SK-2190 Accessory Cabinet. Follow these steps to properly mount the SK-5280 into the SK-2190 cabinet: 1. Mount the remote cabinet using the cabinet mounting holes. See Figure 3-16.
Model SK-5208 Installation Manual 151204 C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and 4 respectively. Relay Rating 2.5A @ 30 VDC/120 VAC Figure 3-17 Relay Wiring on the SK-5280 Note: Figure 3-17 uses A7 and T7 to activate relays 3 and 4 as an example. However, any of the outputs can be used to trip any of the relays. 3.14.3.
Control Panel Installation 3.14.4 151204 Model SK-5217 Zone Expander Installation The Model SK-5217 provides the SK-5208 with ten additional Class B (style B) zones. The SK-5217 connects to the SK-5208 control panel via the SBUS as shown in Figure 3-19. SK-5217 Control Panel Supervised Power Limited Class B Figure 3-19 SBUS Connections 3.14.4.1 Zone Inputs Figure 3-20 and Figure 3-21 shows how to wire detectors to the SK-5217. Use a 4.7k end of line resistor for each Class B circuit.
Model SK-5208 Installation Manual 151204 Voltage:17.5 to 28 VDC Device ID Dip Switches Supervised Power Limited 4.
Control Panel Installation 151204 3.14.4.2 Mounting Instructions The SK-5217 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet. Mounting the SK-5217 into SK-5208 Cabinet Follow these steps to properly mount the SK-5217 zone expander into the SK-5208 cabinet: 1. Remove power from the control panel. 2. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-22. Figure 3-22 Installing the SK-5217 Into the SK-5208 Cabinet 3.
Model SK-5208 Installation Manual 3. 151204 Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23. Mounting Holes Mounting Holes Figure 3-23 Model SK-5217 Remote Installation 4. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19. 5. Set the ID code (see Section 3.14.1). If ID code 1 is selected the SK-5217 will input zones 11 - 20. If ID code 2 is selected the SK-5217 will input zones 21 - 30. 6.
Control Panel Installation 2. 151204 Remove the 5824 circuit board from the base by pushing outward on the base snap retaining tabs and lifting the circuit board out. Mounting Holes Snap Retaining Tabs Mounting Holes Base Figure 1: 5824 Circuit Board And Plastic Base 3. Mount the plastic base. 4. Replace the circuit board in the plastic base. Note: It may be necessary to connect the wiring to the circuit board before the board is replaced in the base. See Section 3.14.5.2. 5.
Model SK-5208 Installation Manual 151204 Serial Port 5824 Parallel Port ID Selector Switches Figure 3-25 Model 5824 Serial/Parallel Port, and ID Selector Switch location 3.15 Special Applications 3.15.1 Model 5220 Direct Connect Module The 5220 Direct Connect module can be used with the SK-5208 to meet NFPA 72 standards. The 5220 requires four connections to the SK-5208 and provides outputs for city box and polarity reversal applications. The 5220 cannot be used for sprinkler supervisory.
Control Panel Installation 3. 151204 Program NAC #4 to be direct connect from the NAC Options menu. Relay #4 will automatically be configured to indicate system troubles. Note: It is not possible to reset the remote indication until you clear the condition and reset the SK-5208. 5220 City Box Coil Resistance 14.5 Supervised for Opens and Ground Faults Control Panel Figure 3-26 City Box Connection 3.15.1.
Model SK-5208 Installation Manual 4. 151204 If necessary, adjust circuit current using potentiometer R10 on the 5220 board. Normal circuit current is 4to-8 mA with a 1k ohm remote station protected premise unit. Maximum circuit resistance is 3k ohm. Trouble Contacts Supervised For Opens and Ground Faults Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.
Control Panel Installation 5. 151204 Program NAC 3 cadence as Steady (see Section 4.2.3). Trouble Contacts Supervised For Opens and Ground Faults See Table 3-4 for electrical ratings. All Other Circuits Supervised Power Limited Note: The term FACP Term. refers to terminals on the SK-5208 Figure 3-28 Wiring the Keltron 3158 to the SK-5208 3.15.
Model SK-5208 Installation Manual 1. 151204 Wire the MR-201/T as shown in Figure 3-29. Intended for Connection to a Polarity Reversal Circuit of a Remote Station Receiving Unit Having Compatible Rating. Figure 3-29 Wiring the MR-201/T 2. Program the NAC circuit as a non silence NAC (see Section 4.3).
151204 Section 4 Programming The SK-5208 control panel can be programmed from either the on-board annunciator or the SK-5235 remote annunciator. You must be in Programming Mode to program the control panel. 4.1 Keypad Operation During Programming This section describes the function of the buttons on the keypad while in program mode. Operation/Button Operation/Description Enter Step Programming mode Press 2, 7, ENTER, followed by installer level code (the factory programmed code is 123456 or 5208).
Programming 4.1.1 151204 Special Characters Special characters are characters used while dialing such as pause, *, #, or 2nd dial tone. Table 4-1 list the Special characters and what they mean. Table 4-1: Special Characters To Enter: 4.1.
Model SK-5208 Installation Manual 4.2 151204 Programming Flow Figure 4-2 provides an overview of the programming menu flow. Figure 4-3 through Figure 4-13 illustrate the programming flow within each option. The arrows indicate how to maneuver through programming.
Programming 4.2.1 151204 Zone Options Figure 4-3 illustrates, in more detail, the programming flow when in the zone options menu.
Model SK-5208 Installation Manual 4.2.2 151204 Misc System Option Figure 4-4 illustrates, in more detail, the programming flow when in the misc system menu.
Programming 4.2.3 151204 NAC Cadence Figure 4-5 illustrates, in more detail, the programming flow when in the NAC cadence menu. Figure 4-5 NAC Cadence 4.2.3.1 Cadence Patterns The cadence patterns shown in Table 4-2 can be selected for NAC outputs. Each NAC can select an output pattern. Special cadence patterns can be selected for fire drill or an auxiliary input switches used with the system. Table 4-2: Cadence Patterns # Name 1 Constant Output 2 March Code Output 3 ANSI S-3.
Model SK-5208 Installation Manual 4.2.4 151204 NAC Options Figure 4-6 illustrates, in more detail, the programming flow when in the NAC options menu.
Programming 4.2.5 151204 Relay Options Figure 4-7 illustrates, in more detail, the programming flow when in the relay options menu.
Model SK-5208 Installation Manual 4.2.6 151204 User Code Figure 4-8 illustrates, in more detail, the programming flow when in the user code menu.
Programming 4.2.7 151204 Account Figure 4-9 illustrates, in more detail, the programming flow when in the account menu. Figure 4-9 Account Programming Menu Must The dialer MUST report events in this family to this account. Selecting Must makes an account a primary reporting account. The dialer will try to report the event to the primary account until it exceeds the “Account Tries” value.
Model SK-5208 Installation Manual 4.2.8 151204 Computer Options Figure 4-10 illustrates, in more detail, the programming flow when in the computer options menu. Figure 4-10 Computer Options Programming Menu Note: Computer CIC & Phone can also use special characters as described in Section 4.1.1. 4.2.8.1 Computer Code In order to remote download to a control, the computer code programmed in the panel, and the computer code used in the downloading software must match.
Programming 4.2.9 151204 Line Options Figure 4-11 illustrates, in more detail, the programming flow when in the line options menu. Figure 4-11 Line Options Programming Menu Note: Line prefix can also use special characters as described in Section 4.1.1.
Model SK-5208 Installation Manual 4.2.10 151204 Misc Reporting Figure 4-12 illustrates, in more detail, the programming flow when in the miscellaneous reporting menu.
Programming 4.2.11 151204 5280 Outputs Figure 4-13 illustrates, in more detail, the programming flow when in the SK-5280 outputs menu. Figure 4-13 5280 Outputs Programming Menu If Zones 1-10 is selected then the SK-5280 will output when alarms and troubles occur for zones 1 through 10. If Zones 11-20 is selected then SK-5280 will output when alarms and troubles occur for zones 11 through 20. If Zones 21-30 is selected then the SK-5280 will output when alarms and troubles occur for zones 21-30.
Model SK-5208 Installation Manual 4.2.12 151204 5824 Expander Options Figure 4-14 illustrates, in more detail, the programming flow for the 5824 serial/parallel module.
Programming 4.2.13 151204 DST/Clk Options Figure 4-16 illustrates the programming flow for the Daylight Saving Time (DST) and clock source options.
Model SK-5208 Installation Manual 4.3 151204 Programming Options Table 4-4 list all the programming options and the items that can be modified within those programming option menus. Note: Programming options that have a # in the Programming Options column have multiple programmable components. See Section 4.1.2 for additional information. Table 4-4: Programming Options Programming Option Menu Item Choices Default Comments Programmable through SKSS downloading software.
Programming 151204 Table 4-4: Programming Options Programming Option Menu Item Choices None Default X Prealarm Zone (1-30) # Options Crossalert A Crossalert B Interlock A Interlock B Manual Release A Manual Release B See Section 5.5. See Section 5.5.
Model SK-5208 Installation Manual 151204 Table 4-4: Programming Options Programming Option Menu Item 5217 Expanders Misc System (cont.) Plex Door NAC (1-4) # Cadence Silence NAC Fire NAC Prealarm NAC Aux NAC Waterflow NAC Supervisory NAC NAC Options Choices 1 2 No Default X Yes Constant March Code ANSI S-3.41 Code All NACs Single Stroke BI California Code System Sensor Sync. Wheelock Sync. Gentex Sync. Faraday Sync. Amseco Sync.
Programming 151204 Table 4-4: Programming Options Programming Option NAC Options Relay Options Menu Item Choices Fire Drill NAC 1234 All NACs selected Silence Relay ____ No Relays selected Fire Relay 1___ Prealarm Relay ____ Aux Relay ____ Waterflow Relay ____ Superv Relay ____ Crossalert A Relay _ _ _ _ Release A Relay ____ Crossalert B Relay _ _ _ _ Relay 1 selected No Relays selected No Relays selected No Relays selected No Relays selected No Relays selected No Relays selected No
Model SK-5208 Installation Manual 151204 Table 4-4: Programming Options Programming Option Menu Item Choices Default Account <#> # Enter a 6-digits number 1: 105208 2: 205208 3: 305208 4: 405208 CIC <#> # Enter up to 8 digits Phone <#> # Enter up to 16 digits SIA8 SIA20 Contact ID SK4/2 1400 3/1 1400 3/1 2300 1 to 5 No Yes Must No Yes Must Account # Format Account # Tries Account (1-4) # Report # Alarm Report # Restore No Report # Trouble 3 X X X Must Report # Test X Yes Must Compute
Programming 151204 Table 4-4: Programming Options Programming Option Computer Options Menu Item Computer Code Choices Default 1 to 6 digits 0 Not Used X DTMF/USA Rotary USA Rotary Only Line # Dial Type DTMF Only DTMF/Euro Rotary Euro Rotary Only Line (1-2) # Options No Line # GS Line # Rings X Yes 0 - 15 Line 1: 2 Line 2: 10 No X Line # Ans Mach Yes Line # Prefix Up to 8 digits Test Time 00:00 - 23:59 12:00 Test Interval Every 4 Every 6 Every 12 Every 24 X 0-30 Hours 2 No X
Model SK-5208 Installation Manual 151204 Table 4-4: Programming Options Programming Option Menu Item *3/1 Alarm *3/1 Alarm Rst Misc Reporting Choices 0-9 * Event code for 3/1 and 4/2 reporting formats.
Programming 151204 Table 4-4: Programming Options Programming Option 5824 Expander Menu Item Parity Choices None Even Odd Default X Comments Select the Parity that your printer requires for proper communication. Consult installation manual for your printer. The panel’s AC line frequency is selectable for 60, 50 Hz, or Internal. AC Frequency feature dictates how the control panel will calculate time based on the AC line frequency used in the installation site.
151204 Section 5 Operation To operate the SK-5208 you can use either the on-board touchpad or the Model SK-5235 Remote Annunciator. Figure 5-1 Model SK-5235 Remote Annunciator Important! Upon initial power up there is a 45 second delay before the initiation circuits become active. The system will be ready to receive alarms once the display indicates “System Normal” 5.1 Installer & User Keys An installer key ships with the panel and an operator’s key ships with the SK-5235 (Figure 5-2).
Operation 5.2 151204 On-board Touchpad and SK-5235 Operation Basic operations for the on-board annunciator (touchpad) and SK-5235 are described in Table 5-1. If you are using an annunciator key or the Flex Door option, you are not required to enter a code for operator level functions. If no keys are pressed for 4 minutes while in program mode, the system will time out and resume normal operation.
Model SK-5208 Installation Manual 151204 Also displays Firmware number and revision as shown in Figure 5-3. Control Firmware Number Revision Dialer Firmware Number Revision Figure 5-3 Firmware Numbers and Revisions 5.3 Acknowledge Operation To display an event, first press the ENTER, while the event is displayed the event can be acknowledged by pressing the ENTER button again. No code is required to acknowledge events.
Operation 5.5 151204 Releasing Operation This system can perform two types of releasing operation, cross alarm releasing, and double interlock releasing operations. Install in accordance with NFPA 72 paragraphs 3-8.3.2.3.3 and 3-8.3.2.3.3.2. 5.5.1 Cross Alarm Operation The fire alarm control panel has two cross alert groups to select from, Cross Alert A and Cross Alert B that accommodate releasing water systems.
Model SK-5208 Installation Manual 151204 A Model 7641 EOL resistor/diode assembly is required when connecting the FACP to releasing solenoids. The 7641 allows the FACP to supervise the wiring between its NACs and the releasing solenoid. Table 5-4: Approved Releasing Solenoids Manufacturer Asco Part Number T8210A107 8210G207 Rating 24 VDC, 16.8 W 24 VDC, 10.6 W Figure 5-4 Solenoid Wiring Configuration Do not mix cross alarming zones with smoke verification zones.
Operation 5.5.2 151204 Double Interlock Releasing Operation A typical double interlock releasing system would be programmed with a minimum of two zones selected for “Cross Alert A”, one zone selected as “Man. Release A”, and one selected as “Interlock A”. Additional zones can be selected as Cross Alert or Manual Release. This double interlock system requires both cross alert and manual release verification zones. A single manual release and interlock zone can be used without any cross alert zones.
Model SK-5208 Installation Manual 5.7 151204 System Testing This section describes operation of fire drills, zone testing, and the 24-hour automatic test. 5.7.1 Fire Drills Fire drills can be run from either the on-board touchpad or the Model SK-5235 Remote Annunciator. To initiate a fire drill, press 20 ENTER + Code. The system will sound an alarm and report a fire test. To end the fire drill, press RESET + Code. 5.7.2 Walk Test The walk test is designed to be used for on-site testing only.
Operation 5.8.1 151204 Programming From a Remote Computer Location The panel can communicate with a Up/Downloading computer using two methods. The control panel can call the programming computer or the programming computer can call the control panel. The programming information for the control panel will be stored in the queue of the downloading software SKSS P/N 5660. This data packet will have been pre-configured for the control panel that you are about to program.
Model SK-5208 Installation Manual 151204 you do not select a name for the file, it will be automatically named with the panel model and the date and time of the download. For downloads, the latest saved version of the file will be sent. This means if the file you want to send is currently open and has been changed, save it before you attempt to download. Account Number:Enter the panel account number. Computer Code:Enter the code that allows access to the panel from a PC.
151204 Section 6 Reporting The SK-5208 can transmit information in four different formats. This section describes the four basic reporting formats of the SK-5208 and the codes that they send to a central station receiver. Of these four formats some of the formats offer a more specific selection for that format. For example, you can select a 3/1 format that requires a 1400 or 2300 Hz handshake, or SIA format that can handle 8 or 20 events per call.
Reporting 6.2 151204 Reporting Codes Table 6-2 list the events sent by the SK-5208 and the code that is sent for that event by the type of reporting format used. Note: Codes under in the SK4/2 and 3/1 1400 & 2300 column are the codes programmed for 3/1 reporting formats in Misc Reporting. See Section 4.2.10 for Misc. Reporting options and Table 6-3 for default 3/1 format reporting values.
Model SK-5208 Installation Manual 151204 Table 6-2: Event and Reporting Code by Format Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID Fire Trouble/Clean-Me Trouble 1-30 FT1 - FT30 T1 - T0 Trouble Code 1 373 001 - 1 373 030 Fire Unbypass FU1-FU30 R1 - R9 Restore Code 3 571 011 - 3 571 030 Heat Alarm KA1-KA30 A1 - A9 Alarm Code 1 114 001 - 1 114 030 Heat Bypass KB1-KB30 T1 - T0 Trouble Code 1 570 011 - 1 570 030 Heat Alarm Restore KH1-KH30 AR1 - AR0 Alarm Restore Code 3 114 001
Reporting 151204 Table 6-2: Event and Reporting Code by Format Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID Water Bypass 1-30 WB1-WB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030 Water Alarm Restore 1-30 WH1-WH30 AR1 - AR0 Alarm Restore Code 3 154 001 - 3 154 030 Water Trouble Restore 1-30 WJ1-WJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030 Water Trouble 1-30 WT1-WT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030 Water Unbypass 1-30 WU1-WU30 R1 - R0 Restore Code 3 570 001 - 3 5
Model SK-5208 Installation Manual 6.2.1 151204 Default Settings for 3/1 Format Table 6-3 displays the default settings which are set in the Misc. Reporting section of Programming.
151204 Section 7 Troubleshooting This section of the manual contains information that can be used to isolate and correct installation problems encountered in the field. 7.1 System Error Messages Table 7-1 contains a list of possible error messages along with their meaning and possible solution. Table 7-1: Error Messages Error Message Description Solution FLASH Defaulted On power up the SK-5208 will check the flash for an “option record”.
Troubleshooting 151204 Table 7-1: Error Messages Error Message Description Solution Aux Pwr Trb The SBUS power terminal (27) is supervised and will display this message when the voltage between SBUS power and circuit ground drops below 20 VDC. This may occur if the maximum current rating (1Amp) for this circuit is exceeded. AC Trb This message is displayed when the AC voltage drops below 98 VAC. Check the AC power connection.
Model SK-5208 Installation Manual 7.3 151204 Earth Fault Resistance Table 7-2 list the earth fault resistance values for each applicable terminal on the FACP. Table 7-2: Earth Fault Resistance Values by Terminal Function Zone 1 input.
151204 Appendix A Compatible Devices This section of the manual lists devices (smoke detectors and notification appliances) that are compatible with the SK-5208. Contact Silent Knight if you have a question about whether a device not listed here is compatible. A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized.
Compatible Devices 151204 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual 446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M.
Model SK-5208 Installation Manual 151204 Table A-1: Compatible Notification Appliances Manufacturer Faraday (cont.
Compatible Devices 151204 Table A-1: Compatible Notification Appliances Manufacturer Faraday (cont.
Model SK-5208 Installation Manual 151204 Table A-1: Compatible Notification Appliances Manufacturer FCI (cont.
Compatible Devices 151204 Table A-1: Compatible Notification Appliances Manufacturer Model WGEC24-75W Gentex (cont.
Model SK-5208 Installation Manual 151204 Table A-1: Compatible Notification Appliances Manufacturer System Sensor (cont.
Compatible Devices 151204 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Type AH-12 x Horn AH-24 x Horn AH-12WP x Horn Weatherproof AH-24WP x AMT-241575W x Horn Weatherproof AMT-24MCW x Multi-Tone Horn Strobe x Mutli-Tone Horn Strobe x Multi-Tone Horn Strobe AMT-241575W-NYC x AMT-12/24 x Multi-tone Horn AMT-12/24 NYC x Multi-tone Horn AS-121575W Wheelock Visual x Horn/Strobe NH-12/24 x x Horn AS-241575W x x Horn/Strobe AS-24MCC x x H
Model SK-5208 Installation Manual 151204 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type MTWPA-2475W x x Multitone Horn Strobe MTWPB-2475W x x Multitone Horn Strobe MTWPG-2475W x x Multitone Horn Strobe MTWPR-2475W x x Multitone Horn Strobe MTWPA-24MCCH x x Multitone Horn Strobe ZNH x NS-121575W x x Horn/Strobe NS-241575W x x Horn/Strobe NS-24MCW x x Horn/Strobe NS-24MCC x x Horn/Strobe NS-24MCCH x x Horn/Strobe ZNS-MCW x
Compatible Devices 151204 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type RSSWPG-24MCCH x Strobe Weatherproof RSSWPR-24MCCH x Strobe Weatherproof RSSWP-2475W x Strobe Weatherproof RSSWP-2475C x Strobe Weatherproof RSSWP-24MCWH x Strobe Weatherproof ZRS-MCWH x Strobe ZRS-24MCC x Strobe ZRS-24MCCH x MB-G6-24 Strobe Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell Wheelock MB-G10-12 Motor Bell (cont.
Model SK-5208 Installation Manual A.2 151204 Two-Wire Smoke Detectors The table below lists two-wire smoke detectors that are compatible with the SK-5208 and SK-5217 zone expander. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. Manufactu rer Enhanced Mode Compatible Model Name or Number (Base model name or number in parentheses.
Compatible Devices Manufactu rer ESL FCI Grinnell Fire Protection 151204 Enhanced Mode Compatible Model Name or Number (Base model name or number in parentheses.
Model SK-5208 Installation Manual Manufactu rer Hochiki KiddeFenwal System Sensor Enhanced Mode Compatible 151204 Model Name or Number (Base model name or number in parentheses.
Compatible Devices A.
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
Model SK5208 Basic Operating Instructions These Instructions must be framed and displayed next to the SK-5208 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Operation Task to Perform Press 0 ENTER them enter a code if prompted. The system will perform a display lamp test and a communication test. Displays Firmware Revisions. Press 1 ENTER or RESET then enter a code if prompted.
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.