Specifications
Programming
151018 5-23
5.4.4 System Options
In System Options you can configure the backup battery configuration, the receiver ID
number, and the normal state of the auxiliary relay. Table 5-7 list the available choices and
gives a description of those choices.
Figure 5-8 System Options Display
Table 5-7: System Options
General
Options
Items
Level 1 Choices Level 2 Choices Level 3 Choices Comments
System Options
Battery Backup Cfg
No Battery Bkp
No charging current applied to battery
circuit. Receiver will not test battery
output or give trouble annunciations.
Default. See Section 5.4.4.1.
DC Bkp
No charging current applied to battery
circuit. Typically used for systems that
use a UPS (uninterrupted power
supply) for backup battery power. See
Section 5.4.4.1.
Battery Bkp
Charging current applied to battery
circuit. See Section 5.4.4.1.
Receiver Mode
Single
Select this option if using a single
receiver. Default. See Section 5.4.4.2.
MstrPrn
If this is selected, data is printed
through the printer attached to this
receiver when the automation system
fails. See Section 5.4.4.2.
SlvPrn
If the automation system fails any data
from receiver selected as Slave Printer
will be sent to the receiver designated
as Master Printer. See Section 5.4.4.2.
MstrAuto
If selected all data sent through this
receiver to the automation system. See
Section 5.4.4.2.
SlvAuto
If selected all data is sent to the master
receiver and then onto the automation
system. See Section 5.4.4.2.
Receiver ID No. 01-99 Default: 01. See Section 5.4.4.3.