Specifications
Model 9800 Central Station Receiver Installation/Operation Manual
A-4 151018
General Options
(cont.)
Communication
(cont.)
Annunciator
Configuration
Printer Yes or No Yes = will annunciate if an event, trouble or fault condition
occurs.
No = no annunciation if an event, trouble or fault condition
occurs.
Default for all options: Yes.
See Section 5.4.3.6.
* Listen In option must be set to No for UL installations.
Bkp Printer Yes or No
Auto Comp Yes or No
Bkp Auto Comp Yes or No
Battery Yes or No
Device Yes or No
Line Fault Yes or No
AC Power Yes or No
Buffer Full Yes or No
Listen In Yes or No
Call Pending Yes or No
Aux Relay Cfg
Options the same as Annunciator Configuration.
See Section 5.4.3.7.
* Listen In option must be set to No for UL installations.
System Options
Battery Backup Cfg
No Battery Bkp
No charging current applied to battery circuit. Receiver will not
test battery output or give trouble annunciations. Default. See
Section 5.4.4.1.
DC Bkp
No charging current applied to battery circuit. Typically used for
systems that use a UPS (uninterrupted power supply) for backup
battery power. See Section 5.4.4.1.
Battery Bkp
Charging current applied to battery circuit. See Section 5.4.4.1.
Receiver Mode
Single
Select this option if using a single receiver. Default. See Section
5.4.4.2.
MstrPrn
If this is selected, data is printed through the printer attached to
this receiver when the automation system fails. See Section
5.4.4.2.
SlvPrn
If the automation system fails any data from receiver selected as
Slave Printer will be sent to the receiver designated as Master
Printer. See Section 5.4.4.2.
MstrAuto
If selected all data sent through this receiver to the automation
system. See Section 5.4.4.2.
SlvAuto
If selected all data is sent to the master receiver and then onto the
automation system. See Section 5.4.4.2.
Receiver ID No. 01-99 Default: 01. See Section 5.4.4.3.
Bad Data Blocks
Strip Bad
An indicator is sent to the automation computer that indicates a
bad data block was received. Default.
See Section 5.4.4.4
Send Bad
Same as Strip Data except the bad data block is sent with the
indicator.
See Section 5.4.4.4
Table A-1: Programming Quick Chart
Program Mode
Options
Choices Choices Choices Choices Comments