Specifications
System Operation
151295 8-11
Trouble A system trouble 
condition 
occurs.
The dialer seizes control of the phone line 
and calls the central station.
The on-board annunciator sounds a loud, 
pulsing beep in the sequence one second 
on, nine seconds off.
SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this 
one.
Press   (down arrow) to view the trouble. A screen 
similar to this one displays.
Press   and enter an access code (or activate 
the key) to silence the annunciator.
Once the trouble condition has been fixed, the 
system will restore itself automatically.
Prealarm A single detector 
trips in a 2-
Count zone. (2-
Count means 
two detectors 
must trip before 
an alarm is 
reported.)
Touchpad PZT beeps.
The LCD displays a screen similar to this 
one. 
Press   (down arrow) to view the prealarm. A 
screen similar to this one displays.
All system operations are available in this mode. 
Reset
The 
button is pressed 
followed by a 
valid code or 
rotation of the 
key.
All LEDs are on briefly then the LCD 
displays "ALARM RESET IN 
PROGRESS". If the reset process 
completes normally, the date and time 
normal mode screen displays.
Menus are not available during the reset process.
Silenced An alarm or 
trouble 
condition has 
been silenced 
but still exists. 
To silence 
alarms and 
troubles, press 
 followed 
by the Installer 
or User Code or 
rotate the key.
SYSTEM SILENCE LED is on. SYSTEM 
TROUBLE, SUPERVISORY or 
GENERAL ALARM LED (depending on 
condition) is on. The annunciator (and any 
notification devices attached to the 
system) will be silenced.
Press   (down arrow) to view the location of the 
alarm or trouble. When the condition no longer 
exists, the SYSTEM SILENCED and SYSTEM 
TROUBLE LED, SUPERVISORY or GENERAL 
ALARM LEDs turn off.
Table 8-2: Operation Modes of FACP
Operation 
Mode
Occurs When System Behavior In This Mode You Can