Specifications
Programming
151295 7-21
SLC Loop
(cont.)
SWITCH
(cont.)
RESET
System-level switch provides an alternate way to reset 
the system; same effect as pressing the Reset key.
PAS_ACK
Positive acknowledge switch. This switch must be used 
in zones programmed as Positive Alarm Sequence (see 
Table 7-1).
If an acknowledge switch closes when an alarm or 
trouble condition is not already in progress, a trouble 
will occur. 
You must use a UL listed normally open, momentary 
switch type. The switch must be rated at 5V, 100 mA 
(minimum) and be used with an EOL resistor for 
supervision.
ZN_AUX1
Latching Use these switch types if you want to monitor special 
zone-level conditions.
Non Latching
ZN_AUX2
Latching
Non Latching
SYS_AUX1
Latching Use these switch types if you want to monitor special 
system-wide conditions.
Non Latching
SYS_AUX2
Latching
Non Latching
DETECT SW
Used to monitor conventional 4-wire detectors, a 
contact closure will generate a detector alarm event.
TAMPER
Latching Performs identically to a supervisory switch, but will be 
indicated as a tamper switch on the LCD annunciator.
Non Latching
MAN REL
Latching Manual release switch, typically a pull station.
Non Latching
ILOCK
Latching Interlock release switch input.
Non Latching
RELAY
OUTPUT PT Select Group
Output Point, a general use relay type. Use for 
applications requiring a relay, such as elevator recall.
AUX RESET
Use for auxiliary power, resettable applications. See 
Section 4.12.2.3 to learn how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For 
example, if you were using an auxiliary power supply 
for door holders, you would use this option. See Section 
4.12.2.1 for a description of how this option operates.
Table 7-4: Point Programming
Module Type
Type 
Selection
Function
Latching 
Option
Comments