User Guide

CLU2 CLU3
Dimensions
2-5/8"
(77mm)
2-5/8"
(77mm)
10 -1/4"
(260mm)
10 -1/4"
(260mm)
4-3/4"
(120 mm)
4-3/4"
(120 mm)
Performance
MH
S
W
Compac CLU2/3 emergency unit performance
80/50/20 Reectance
10/10/10 Reectance
Center-to-Center 3' Path 6' Path 3' Path 6' Path
CLU3 Unit 76' 76' 75' 75'
CLU2 Unit 76' 60' 63' 55'
Single Unit Coverage 3' Path 6' Path 3' Path 6' Path
CLU3 Unit 64' 64' 61' 57'
CLU2 Unit 56' 52' 48' 40'
†Based on 6ft corridor and 9ft ceiling height and a mounting height of 7.5ft.
‡Based on 200ft by 200ft open area and 30ft ceiling height.
CLU2/CLU3 Compac emergency unit
Compac_emerg_CLU2_3 www.chloride-lighting.com 02/21 page 2 of 3
Meets Life Safety Code Illumination standard average of 1.0 FC, no point less than 0.1 FC max to min ratio of 40:1.
Assumes open space with no obstructions. NFPA 101, Life Safety Code matches California Fire Code of Regulations, Title 24.
Normal operation (o/standby) is not to be confused with emergency operation.