User Manual
CLC Canopy mount Pendant Mount Canopy
Dimensions
13 3/4 "
(350mm)
2-1/8"
(55 mm)
8-11/16"
(220 mm)
Performance
Meets Life Safety Code Illumination standard average of 1.0 FC, no point less than 0.1 FC max to min ratio of 40:1.
Assumes open space with no obstructions. NFPA 101, Life Safety Code matches California Fire Code of Regulations, Title 24.
Normal operation (o/standby) is not to be confused with emergency operation.
MH
W
L
Compac CLC exit/unit combo performance
80/50/20 Reectance
†
10/10/10 Reectance
‡
3' Path 6' Path 3' Path 6' Path
Single Unit Coverage
56' 52' 48' 40'
Center-to-Center
76' 60' 63' 55'
†Based on 6ft corridor and 9ft ceiling height and a mounting height of 7.5ft.
‡Based on 200ft by 200ft open area and 30ft ceiling height.
5-7/8"
(150mm)
1-3/4"
(44mm)
1-3/8"
(34mm)
4-5/16"
(33mm)
4-9/16"
(116mm)
1"
(25mm)
Compac_combo_CLC www.chloride-lighting.com 02/21 page 2 of 3