Installation guide
Modifications reserved Page 33/82
OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 – 120 - 150 kVA
5. Printer Set-up
The UPS is capable of communicating to a serial printer, to printout disparate information.
Please be sure to have a serial printer, that is a printer with a serial RS232 interface.
This is the only printer-interface supported by the UPS.
PRINTER SETUP
Baud=24
00 Parity=O
Bits=8 Handshake=XON
Print All = N
metering
alarms
parameters
+
–
ok
Baud Rate This parameter controls the baud rate used for data transmission.
Although different values can be selected, you must select 2400 Baud, which is the
only valid parameter.
Parity This parameter controls the parity used for data transmission.
Odd (O) even (E) and “no parity” (X) can be selected.
Nevertheless the only valid value is NO PARITY (X).
Bits This parameter controls the length of the data word on the serial line during data
transmission 7 or 8 bits are offered as choice.
Please select 8 bits, as this is the only valid value.
Handshake This parameter is used to determine the communication protocol used when printing.
Valid values are “XON” standing for the XON/XOFF protocol or “NO” standing for any
protocol.
Print All This parameter Y/N is used to print all the available information in the sequence
metering, alarms, user and service parameters.
NOTE !
Please configure your printer with the following parameters: 2400/8/N (2400 bits/sec, 8
bits, no parity).
6. Printer commands
PRINTER COMMANDS
Print Measures = N
Print Alarms = N
Print Parameters = N
metering
alarms
parameters
+
–
ok
Print Measures This Y/N parameter is used to print only the measurement data.
Print Alarms This Y/N parameter is used to print only the sequence of all Alarms/Events.
Print Parameters This Y/N parameter is used to print only the list of User and Service Parameters
NOTE !
After each printing command the corresponding parameter will be set again to N.