Installation guide

Modifications reserved Page 26/82
OPM_SGS_USM_M10_M15_0US_V030.doc Operating Manual SG Series 100 120 - 150 kVA
6.3 PARAMETERS
The parameters mode is entered any time the parameters button is pressed.
The LCD will display a series of screens containing the user parameters, accessible without password
protection.
The buttons perform the following functions:
metering Abandon parameters mode and enter metering mode.
alarms Abandon parameters mode and enter alarms mode.
parameters Scroll forward to the next screen.
+ Scroll forward to the next screen.
Select from the current screen the parameter to edit.
ok Start the editing for the currently selected parameter.
NOTE !
During parameters mode there is no means to perform scroll back on the display.
Example of operation within parameters mode:
Purpose: to correct a wrong telephone number previously stored in Tel2.
1 – Entering parameters mode (parameters). The first screen is displayed.
DATE AND TIME
D M Y
Date: 01
.01.2006
Time: 12:45:07
metering
1
alarms
parameters
+
ok
2 – Scroll to the next screen (+). The second screen is displayed.
PROTOCOL SETUP
Modem enabled=N
Init=BEQV1X3&D0S0=2
Alarm= N Delay=22s
metering
2
alarms
parameters
+
ok