SGT5000_100-150_UPS_GE01 GE Digital Energy Power Quality Operating Manual Uninterruptible Power supply Digital Energy™ SG Series 100 – 120 – 150 kVA 480 VAC UL / Series 0 Manufactured by: GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 www.gedigitalenergy.
Model: SG Series 100 – 120 - 150 kVA / Series 0 Issue by Product Document Department – Riazzino - CH Date of issue: 11/12/2008 File name: OPM_SGS_USM_M10_M15_0US_V030 Revision: 3.0 Identification No.: Up-dating Revision Concerns Date 2.0 House-style GE Consumer & Industrial 01/30/2006 3.0 GE Digital Energy – Power Quality 11/12/2008 COPYRIGHT © 2008 by GE Consumer & Industrial SA All rights reserved.
Dear Customer, We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE. We trust that the use of the SG Series Uninterruptible Power Supply system, developed and produced to the highest standards of quality, will give you complete satisfaction. Please read carefully the Operating Manual, which contains all the necessary information and describes all you need to know about the use of the UPS.
Preface Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS). It will help eliminate Load disturbances due to unexpected power problems. This Manual describes the function of the UPS module, the purpose and location of the switches, the meaning of the system events related to the front panel indication, and provides procedures for starting and stopping the equipment.
Table of contents Page 1 IMPORTANT SAFETY INSTRUCTIONS ........................................................................................................ 7 2 INTRODUCTION.......................................................................................................................................... 10 3 DESCRIPTION.............................................................................................................................................. 11 3.1 3.
7.2 PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER .................................................................... 48 7.2.1 7.2.2 7.2.3 7.2.4 7.3 PROCEDURES FOR PARALLEL SYSTEM .................................................................................................................................. 52 7.3.1 7.3.2 7.3.3 7.3.4 7.3.5 7.3.6 7.3.7 7.3.8 7.4 COMMUNICATION OPTIONS ..............................................................................................................
1 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models SG Series 100 - 120 - 150 kVA that should be followed during installation and maintenance of the UPS and battery. GENERAL - Move the UPS in an upright position in its original package to the final destination room. To lift the cabinets, use a forklift or lifting belts with spreader bars. Check for sufficient floor and elevator loading capacity. Check the integrity of the UPS equipment carefully.
Safety instructions when working with battery EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY QUALIFIED SERVICE PERSONNEL. INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING THE UPS AND BATTERY. DANGER! Full voltage and current are always present at the battery terminals. The battery used in this system can provide dangerous voltages, extremely high currents and a risk of electric shock. If the terminals are shorted together or to ground they may cause severe injury.
Safety symbols and warnings Safety warnings The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads. The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages. Please pay attention to the meaning of the following warnings and symbols.
2 INTRODUCTION An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a reliable, continuous, disturbance free supply. In case the power provided by the Utility Fails, or exceeds the permitted tolerances, the power to supply the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load) or until the Utility power returns.
3 DESCRIPTION 3.1 BLOCK DIAGRAM AND MAIN ELEMENTS Fig. 3.1-1 Block diagram The SG Series system can be divided into the following main elements: Control System SG Series is designed with microprocessor-controlled signal processing circuits. The interface between the operator and the unit is provided by the monitoring system on the front panel. This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
3.2 OPERATION MODES 3.2.1 Normal operation mode During normal operation, the Rectifier converts input AC power to DC. The DC power provides input power for the Inverter and charging power for the Battery. The Inverter converts the DC power to continuous and regulated AC power, which supplies the critical load. The control panel reports the Battery charge status and the expected backup time with the actual load. Fig. 3.2.1-1 Block diagram normal operation mode 3.2.
3.2.3 Utility recovery operation As soon as the AC input power recovers, the Rectifier will start automatically, supplying DC power to the Inverter and recharging the Battery. If the Inverter was previously shut down due to low Battery, the Load will be initially powered by Utility through the Automatic Bypass. When the Battery is recharged enough to ensure a minimum time of operation with the present load, the Inverter will start automatically and the Load will be transferred back to the Inverter. Fig. 3.
3.3 PARALLEL SYSTEM OPERATION 3.3.1 Introduction to the parallel system Two or more equal power units can be paralleled to increase the output power (paralleling for capacity) or to improve the overall reliability of an UPS system (paralleling for redundancy). The outputs of parallel units are connected to a common power bus, and in normal operation the units connected on the parallel bus share the Load equally.
3.3.2 Features of RPA parallel system The SG Series parallel system is designed to provide a complete Redundant Parallel Architecture, and is free from common equipment. Not only the Inverters are redundant, but also the Bypass functions are designed with redundant modular concept. When one UPS needs maintenance or service, the Load is powered by the other units supplying the Load bus.
3.4 RECTIFIERS PARALLELED ON THE SAME BATTERY NOTE ! A parallel system with a Common Battery for two or more Rectifiers, requires a particular installation and adequate setting of some parameters, (accessible only through password), and can therefore only be done by a qualified engineer from GE. Usually each Rectifier-Inverter Unit runs with its own Battery. In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 3.
3.5 RECYCLING AT THE END OF SERVICE LIFE NOTE ! This product has been designed to respect the environment, using materials and components respecting eco-design rules. It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen Carbon Fluor Clorid). GE, in compliance with environment protection recommends to the User that the UPS equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.
LAYOUT 4.1 LAYOUT SG Series 100 - 120 - 150 kVA SGT5000_100-150_UPS_GE02 SGT5000_100-150_UPS_03 4 1 2 3 4 J2 1 2 3 4 Fig. 4.1-2 SG Series general view with open doors Fig. 4.1-1 SG Series general view Fig. 4.1-4 Control Panel 1 SGT5000_100-150_Customer interface_03 Fig. 4.
5 CONTROL PANEL 5.1 CONTROL PANEL Fig. 5.1-1 Control Panel 5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL inverter on/off inverter on/off Key to switch the Inverter ON ( I ) (This key is also used to reset “total off” if pressed simultaneously with total off push button). Key for Inverter shutdown ( O ) Press key to transfers the Load to Utility. Keep pressed for 5 seconds to shutdown the Inverter. This key is also used as the EPO (Emergency Power Off) reset.
General alarm condition It blinks when one or more alarm is activated. The internal buzzer is ON. The LED remains lighted (with alarm condition still present) and the buzzer stops as the key “mute” has been pressed. alarm LED ON indicates that a regular maintenance service is needed. May be reset by a service technician only. See Section 11 – Maintenance. The LED is ON also when the output switch Q1 is open, indicating that the Inverter is in service mode, not supplying the load.
6 LCD SCREEN The user interface consists of a back lit LCD screen having: • 4 lines with 20 characters (standard version for Latin characters). and • 6 keys (the function is described for each operating mode). The operation is extremely simple and is structured on three important main menus related to the UPS operation, as follows: metering A UPS must offer some metering information for the user to be able to examine the operating status at any time.
6.1 METERING MODE The metering mode is entered any time the metering button is pressed. While in this mode the LCD will display a series of screens containing metering information. In this mode the buttons perform the following functions: metering Scrolls forward to the next screen. alarms Abandons the metering mode and enters the alarms mode. parameters Abandons the metering mode and enters the parameters mode. + Scrolls forward to the next screen. – Scrolls backward to the previous screen.
Rectifier Utility data screen This screen refers to the AC source supplying the Rectifier. This screen displays: • Iout1 = output current Rectifier Bridge. • Iout2 = output current 2nd Rectifier Bridge (optional 12 pulse Rectifiers only). • The voltage levels between the three phases (line-to-line). • The input frequency of the Rectifier. m etering alarm s param eters R EC TIFIER U12=481V Iout1 =133A U23=480V Iout2 = 0A U31=482V f=60.
Load on phases screen 2 This screen displays for each phase: • The Load active power (kW) (for RPA: total value of Parallel System). • The Load apparent power (kVA) (for RPA: total value of Parallel System). metering alarms parameters LOAD ON PHASES L1= 22.37kW 27.97kVA L2= 21.05kW 26.31kVA L3= 20.61kW 25.76kVA + – ok Miscellaneous screen This screen displays: • The temperature of the Inverter Bridge. • The total operating time for the UPS (in hours).
6.2 ALARMS The alarms mode is entered any time the alarms button is pressed. The LCD will display a series of screens corresponding to the last 256 events, one event per screen. The buttons perform the following functions: metering Abandons alarms mode and enters metering mode. alarms Next screen. parameters Abandons the alarms mode and enters the parameters mode. + Scrolls forward to the next screen. – Scrolls backward to the previous screen. ok Display the main screen for this mode.
6.3 PARAMETERS The parameters mode is entered any time the parameters button is pressed. The LCD will display a series of screens containing the user parameters, accessible without password protection. The buttons perform the following functions: metering Abandon parameters mode and enter metering mode. alarms Abandon parameters mode and enter alarms mode. parameters Scroll forward to the next screen. + Scroll forward to the next screen. – Select from the current screen the parameter to edit.
3 – Scroll to the next screen (+). The third screen is displayed. metering 3 alarms parameters Tel1:002186394567 Tel1 enabled: Tel2:004017464340 Tel2 enabled: + N N – ok 4 – Move the selection (underscore cursor) to the next parameter in this page (-). metering 4 alarms parameters Tel1:002186394567 Tel1 enabled: Tel2:004017464340 Tel2 enabled: + N N – ok 5 – Move the selection to the next parameter in page (-).
6.4 EDIT MODE The EDIT MODE is entered from the parameters mode when the ok button is pressed. During this mode the LCD will display a special editing screen for the parameter being edited. The screen contents during Edit mode is: • First line: the special operating mode. • Second line: the name of the parameter being edited. • Third line: the current value of the parameter. • Fourth line: contains a condensed help text.
3 – Change the selected character (-). metering 3 alarms parameters EDIT MODE PHONE NUMBER 2 005017464340 + SCROLL - CHANGE + – ok 4 – Change the selected character (-). metering 4 alarms parameters EDIT MODE PHONE NUMBER 2 006017464340 + SCROLL - CHANGE + – ok 5 – Press ok: the screen will return to parameters mode saving the new value.
3 – Change to 4800. metering 3 alarms parameters EDIT MODE PRINTER BAUDRATE 4800 + SCROLL - CHANGE + – ok 4 – Press ok: the screen will return to parameters mode saving the new value. metering 4 alarms parameters PRINTER SETUP Parity=O Baud=4800 Bits=8 Handshake=XON Print All = N + – ok Type 3: Boolean parameters used to simulate command buttons. The Boolean parameters have a range of Yes/No. Only the user performs the modification of the value.
6.5 USER PARAMETERS Pressing the Parameters button displays a series of screens containing the user parameters on the LCD panel. This first parameter level in not protected by password, therefore the user can freely adapt these parameters to their needs. The meaning of the user parameters and their use is described below (buttons performance is described to Section 7.3). 1. Date and Time set-up metering alarms parameters DATE AND TIME D M Y Date: 01.01.
3. Telephone numbers m e te rin g a la rm s p a ra m e te rs Tel1 : Tel1 en ab led : N Tel2 : Tel2 en ab led : N + – ok Tel1 This parameter specifies a first telephone number to be used for modem dial-out. The telephone number has a maximum 39 characters and cannot contain blanks. If the desired number is shorter than 39 characters, the string will finish with blanks. Tel1 enabled This parameter Y/N specifies if the first telephone number will be used for dial-out. Tel2 A second dial-out number.
5. Printer Set-up The UPS is capable of communicating to a serial printer, to printout disparate information. Please be sure to have a serial printer, that is a printer with a serial RS232 interface. This is the only printer-interface supported by the UPS. m etering alarm s param eters PRINTER SETUP Baud=2400 Parity=O Bits=8 Handshake=XON Print All = N + – ok Baud Rate This parameter controls the baud rate used for data transmission.
6.6 EVENTS (ALARMS AND MESSAGES) Each of the following listed events can be displayed on the LCD screen or on PC where the “PowerJump Manager” or “PowerJump DataShield” is installed.
Code Alarms 4115 LOW BATTERY VOLTAGE 4116 HIGH BATTERY VOLTAGE 4117 BATTERY EARTH FAULT 4118 BATTERY FAULT 4130 TURN ON RECT. OR SHUTDOWN UPS 4140 RECTIFIER CONTROL FAILURE 4301 INVERTER FUSES FAILURE 4304 K7 CLOSING FAILURE 4305 K7 OPENING FAILURE 4307 INVERTER TRANSFORMER OVERTEMPERATURE 4308 DC FUSES FAILURE 4309 DRIVER FAILURE 4312 INV.
Code Alarms Meaning 4405 K6 OPENING FAILURE 4406 SSM FAILURE 4408 K8 CLOSING FAILURE 4409 K8 OPENING FAILURE 4410 BYPASS UTILITY OUT OF TOLERANCE 4420 K3 CLOSING FAILURE K6 closed despite an opening command being issued. Signalled by auxiliary contact. A faulty current has been detected in the static-switch causing the opening of the contactor K6 for 10 seconds. After 3 times K6 remains definitively open. The alarm reset can be done only from Service Center.
Code Alarms 4700 DC LOW 4900 LOAD LOCKED ON INVERTER 4955 OVERTEMPERATURE 4998 4999 LOAD OFF DUE TO EXTENT. OVERLOAD LOAD OFF DUE TO UBATT. OR TEMP. Modifications reserved OPM_SGS_USM_M10_M15_0US_V030.doc Meaning Battery voltage is at the lowest limit. Will stay Off Inverter until the battery voltage reaches the value in parameter. The Load is locked on Inverter after 3 Load transfers within 30 seconds. After time out (default 30 seconds) Bypass will be free.
6.6.2 Messages list Code Message Meaning 4002 WATCHDOG RESET The microprocessor has detected an incorrect operation: Transfers the Load on Utility and performs a program reset. The Inverter will restart automatically and will supply the Load. Rectifier Input Utility is again within the admitted tolerance (voltage, frequency and phase). Start of Manual or Automatic Battery Test.
Code Message Meaning 4561 TOTAL OFF DETOUR ON DETOUR OFF COMMAND LOAD ON UTILITY COMMAND LOAD ON INVERTER NO MORE OVERLOAD INVERTER AND UTILITY SYNCHRONIZED COMMAND NOT TO SYNCHRONIZE COMMAND TO SYNCHRONIZE Q1 OPEN Q1 CLOSED Push-button “total off” on the UPS Control Panel has been pressed, with the output circuit switch Q1 closed. The auxiliary contact indicates that Manual Bypass Q2 was closed. The auxiliary contact indicates that Manual Bypass Q2 was opened.
6.6.3 Event report SG Series In case of failure or malfunctioning, before calling the nearest Service Center, please note the most important data of your UPS and the most recent events. In order to make the diagnosis easier from our Diagnostic Centre we suggest you make a copy of this page, fill it out with the requested data and send it by fax. Unit No.: __ __ __ __ __ - __ __ __ __ - __ __ __ __ Series No.: Customer: ...................................…………….....……. Place: ......................…....
7 OPERATION This symbol refers to the operations of a parallel system. NOTE ! Verify for correct input/output cabling before connecting Utility to the UPS. Open only the front door, do not remove any panels. Now you can initiate the start-up procedure of the UPS system. There is no need for specific knowledge if you follow carefully the stepby-step instructions given below. But we recommend, that at least the initial procedure, should be performed by an instructed person.
7.1 PROCEDURES FOR SINGLE UPS 7.1.1 Start-up of the SG Series Verify with open front door: Switch Q1 and Q2 must be open (Pos. O). 1. Connect the Utility power on the UPS. (In case of separate inputs for Rectifier and Bypass, connect both). • Power supply starts up. Indicated with flashing alarm and buzzer sound. • LED’s as indicated will be lit. • Press mute, to reset alarm and buzzer. 2. Close Q1 (Pos. I). • Bypass Utility connects to the output.
7.1.2 Maintenance shutdown (Load on Q2) Initial status: Load supplied from Inverter. 1. Press “inverter off” ( O ) key and hold until the LED inside the Inverter symbol turns OFF. • Load is transferred to Utility. • Inverter shuts down. • LED Inverter must be OFF. The LCD screen must display the status “LOAD ON BYPASS”. 2. Close Q2 (Pos. I). • Load is now supplied parallel through Bypass and Q2. • LED for Manual Bypass lights up. 3. Open Q1 (Pos. O) and then press “total off” button.
7.1.3 From Manual Bypass (Q2) to normal function VFI Initial status: Load supplied from Manual Bypass. 1. Close Q1 (Pos. I). • Bypass connects to Load. LED Load on Bypass lights up. • Rectifier starts automatically and LED in Rectifier symbol and LED Battery charge light up. 2. Open Q2 (Pos. O). • LED Manual Bypass turns OFF. 3. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery . 4. Press “inverter on” ( I ) key.
7.1.4 Complete UPS shutdown (No Load supply) NOTE ! The Load must be disconnected. Initial status: Load supplied from Inverter. 1. Press “total off” button. • Load is disconnected from UPS. • Rectifier is shut down and all output and input contactors will be opened. • LED’s, Rectifier, Inverter and Load are OFF. 2. Open Q1 (Pos. O). • LED service check lights up. 3. Disconnect the Battery from the UPS in case of External Battery. • Wait 5 minutes for DC-Link Capacitors discharge. 4.
7.1.5 Restore to normal operation after “total off” View of the panel after pressing the button “total off”. • All Contacts are open. • Rectifier, Inverter and Static-Switch shutdown. 1. Reset “total off” by pressing and holding the “total off” button and then the “inverter on” ( I ) key simultaneously until Load is supplied from Bypass and the Rectifier starts. • Output connects to Bypass Utility. • Rectifier starts with blinking LED. • At the end of Soft-start the LED remains lit.
7.1.6 Restore to normal operation after EPO (Emergency Power Off) UPS panel after activation of EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS. In this case wait until Utility is again available, then proceed to restart the UPS as described below. Points 1 through 3. UPS panel after activation of EPO (Emergency Power Off) with Utility available. • All Contacts are open. • Rectifier, Inverter and Static-Switch shutdown. 1. Reset the EPO (Emergency Power Off) button.
7.2 PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER When the SG Series functions as a Frequency Converter, the Automatic Bypass and Manual Bypass functions are disabled. Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure. In situations where the UPS needs to be shutdown for maintenance purposes, also the Load must be shutdown or disconnected 7.2.
7.2.2 Complete UPS shutdown (No Load supply) NOTE ! The Load must be disconnected. Initial status: Load supplied from Inverter. 1. Press “total off” button. • Load is disconnected from UPS. • Rectifier is shut down and all output and input contactors will be opened. • LED’s, Rectifier, Inverter and Load are OFF. 2. Open Q1 (Pos. O). • LED service check lights up. 3. Disconnect the Battery from the UPS in case of External Battery. • Wait 5 minutes for DC-Link Capacitors discharge. 4.
7.2.3 Restore to normal operation after “total off” View of the panel after pressing the button “total off”. • All Contacts are open. • Rectifier, Inverter and Static-Switch shutdown. 1. Reset “total off” by pressing and holding the “total off” button and the “inverter on” ( I ) key simultaneously until the Rectifier starts. 2. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery. 3. Press “inverter on” ( I ) key.
7.2.4 Restore to normal operation after EPO (Emergency Power Off) UPS panel after activation of EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS. In this case wait until Utility is again available, then proceed to restart the UPS as described below. Points 1 through 3. UPS panel after activation of EPO (Emergency Power Off) with Utility available. • All Contacts are open. • Rectifier, Inverter and Static-Switch shutdown. 1. Reset the EPO (Emergency Power Off) button.
7.3 PROCEDURES FOR PARALLEL SYSTEM 7.3.1 Parallel System start-up Verify on all Units, with open front door: Switches Q1 and Q2 must be open (Pos. O). 1. Connect the Utility power on all UPS’s. (In case of separate inputs for Rectifier and Bypass, connect both). • Power supply starts up. Indicated with flashing alarm and buzzer sounds. • LED’s as indicated will be lit. • Press mute, to reset alarm and buzzer. First operated unit All other units of the system 2. Close Q1 (Pos. I) on all Units.
4. Press “inverter on” ( I ) key on first unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 5. Press “inverter on” ( I ) key on all other units.
7.3.2 Maintenance system shutdown (Load supplied from Q2 on all Units) Initial status: Load supplied from all Inverters. First operated unit All other units of the system 1. Press “inverter off” ( O ) key on all Units, and hold until the LED inside the Inverter symbol turns OFF. At no redundancy, the system will transfer to Utility supply. First operated unit All other units of the system 2. Close Q2 (Pos. I) on all Units.
7.3.3 From Manual Bypass (Q2) to normal function VFI Initial status: Load supplied from Manual Bypass. All Q2 of the system are closed. First operated unit All other units of the system 1. Close Q1 (Pos. I) on all Units. The Rectifiers will start automatically and at the closure of Q1 of the last Unit, the Bypass of all Units will be activated. First operated unit All other units of the system 2.
4. Press “inverter on” ( I ) key on first unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 5. Press “inverter on” ( I ) key on all other units.
7.3.4 Separate a Unit from the parallel system (System Redundancy) Initial status: Load supplied from all Inverters. First operated unit All other units of the system 1. Press and hold “inverter off” ( O ) key on the Unit to separate, until the LED turns OFF. Load supplied from Inverter(s) of the other Unit(s) of the parallel system. First operated unit All other units of the system 2. Open Q1 (Pos. O) and, only when the LED service check is ON, press “total off” button on the Unit to separate.
7.3.5 Reconnect a Unit to a parallel system 1. Connect the Utility supply on the separated Unit. • Press mute, to reset alarm and buzzer. First operated unit All other units of the system 2. Close Q1 (Pos. I) on the separated Unit. Rectifier starts automatically. First operated unit All other units of the system 3. Connect the Battery, in case of External Battery, to the UPS on the separated Unit by closing the external Battery Switch or Fuses. 4. Press “inverter on” ( I ) key on the separated Unit.
7.3.6 Parallel system shutdown (No Load supply) NOTE ! The Load must be disconnected. Initial status: Load supplied from all Inverters. First operated unit All other units of the system 1. Press “total off” button on any one on the Units. • Load is disconnected from UPS. • Rectifier and Inverter are shut down and all output and input Contactors will be opened. • LED’s, Rectifier, Inverter and Load are OFF. First operated unit All other units of the system 2. Open Q1 (Pos. O) on all Units.
3. Disconnect the Battery, in case of External Battery, from all Units. • Wait 5 minutes for DC-Link Capacitors discharge. First operated unit All other units of the system 4. Disconnect the Utility supply from all Units. • All LED’s are OFF. First operated unit All other units of the system END OF PROCEDURE Modifications reserved OPM_SGS_USM_M10_M15_0US_V030.
7.3.7 Restore to normal operation after “total off” View of the panel after pressing the button “total off”. • All Contacts are open. • Rectifier, Inverter and Static-Switch shutdown. First operated unit All other units of the system 1. Reset “total off” by pressing and holding the “total off” button and then the “inverter on” ( I ) key, on any of the Units simultaneously, until Load is supplied from Bypass and the Rectifiers start. • System output connects to Bypass Utility.
3 Press “inverter on” ( I ) key on first unit. • • • • Soft-start of Inverter, indicated with blinking LED. At the end of Soft-start the LED Inverter remains lit. In case of sufficient output power, the output will transfer to Inverter. UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 4. Press “inverter on” ( I ) key on all other units.
7.3.8 Restore to normal operation after EPO (Emergency Power Off) UPS panel after activation of EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS and LCD screen OFF. In this case wait until Utility is again available, then proceed to restart the UPS as described below Points 1 through 3. UPS panel after activation of EPO (Emergency Power Off) with Utility available. All Contacts are open. Rectifier, Inverter and Static-Switch shutdown.
3. Connect the Battery to all Units by closing the external Battery Switches or Fuses, in case of External Battery. 4. Press “inverter on” ( I ) key on first Unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”.
7.4 PROCEDURES FOR PARALLEL SYSTEM WITH COMMON BATTERY 7.4.1 Parallel System start-up Verify on all Units, with open front door: Switches Q1 and Q2 must be open (Pos. O). 1. Connect the Utility power on all UPS’s. (In case of separate inputs for Rectifier and Bypass, connect both). • Power supply starts up. Indicated with flashing alarm and buzzer sounds. • LED’s as indicated will be lit. • Press mute, to reset alarm and buzzer. First operated unit All other units of the system 2.
4. Press “inverter on” ( I ) key on first unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 5. Press “inverter on” ( I ) key on all other units.
7.4.2 Maintenance system shutdown (Load supplied from Q2 on all Units) Initial status: Load supplied from all Inverters. First operated unit All other units of the system 1. Press and hold “inverter off” ( O ) key on all Units, until the LED inside the Inverter symbol turns OFF. At no redundancy, the system will transfer to Utility supply. First operated unit All other units of the system 2. Close Q2 (Pos. I) on all Units.
7.4.3 From Manual Bypass (Q2) to normal function VFI Initial status: Load supplied from Manual Bypass. All Q2 of the system closed. First operated unit All other units of the system 1. Connect the Battery to all Units by closing the external Battery Switch(es) or Fuses. 2. Close Q1 (Pos. I) on all Units. The Rectifiers will start automatically and at the closure of Q1 of the last Unit, the Bypass of all Units will be activated. First operated unit All other units of the system 3. Open Q2 (Pos.
4. Press “inverter on” ( I ) key on first unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 5. Press “inverter on” ( I ) key on all other units.
7.4.4 Separate a Unit from the parallel system (System Redundancy) Initial status: Load supplied from all Inverters. First operated unit All other units of the system 1. Press and hold “inverter off” ( O ) key on the Unit, to separate, until the LED turns OFF. Load supplied from Inverter(s) of the other Unit(s) of the parallel system. First operated unit All other units of the system 2. Open Q1 (Pos. O) and, only when the LED service check is ON, press “total off” button on the Unit to separate.
7.4.5 Reconnect a Unit to a parallel system 1. Connect the Utility supply on the separated Unit. • Press mute, to reset alarm and buzzer. First operated unit All other units of the system 2. Connect the Battery to the UPS separated by closing the external Battery Switch or Fuses. 3. Close Q1 (Pos. I) on the separated Unit. Rectifier starts automatically. First operated unit All other units of the system 4. Press “inverter on” ( I ) key on the separated Unit.
7.4.6 Parallel system shutdown (No Load supply) NOTE ! The Load must be disconnected. Initial status: Load supplied from all Inverters. First operated unit All other units of the system 1. Press “total off” button on any one on the units. • Load is disconnected from UPS. • Rectifier and Inverter are shut down and all output and input contactors will be opened. • LED’s, Rectifier, Inverter and Load are OFF. First operated unit All other units of the system 2. Open Q1 (Pos. O) on all Units.
3. Disconnect the Battery from all Units. • Wait 5 minutes for DC-Link Capacitors discharge. First operated unit All other units of the system 4. Disconnect the Utility supply from all Units. • All LED’s are OFF. First operated unit All other units of the system END OF PROCEDURE Modifications reserved OPM_SGS_USM_M10_M15_0US_V030.
7.4.7 Restore to normal operation after “total off” View of the panel after pressing the button “total off”. • All Contacts are open. • Rectifier, Inverter and Static-Switch shutdown. First operated unit All other units of the system 1. Reset “total off” by pressing and holding the “total off” button and then the “inverter on” ( I ) key, on any of the Units simultaneously, until Load is supplied from Bypass and the Rectifiers start. • System output connects to Bypass Utility.
3. Press “inverter on” ( I ) key on first unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 4. Press “inverter on” ( I ) key on all other units.
7.4.8 Restore to normal operation after EPO (Emergency Power Off) UPS panel after activation of EPO (Emergency Power Off) with Utility not available, i.e. complete shutdown of the UPS and LCD screen OFF. In this case wait until Utility is again available, then proceed to restart the UPS as described below Points 1 through 3. UPS panel after activation of EPO (Emergency Power Off) with Utility available. All Contacts are open. Rectifier, Inverter and Static-Switch shutdown.
4. Press “inverter on” ( I ) key on first Unit. • Soft-start of Inverter, indicated with blinking LED. • At the end of Soft-start the LED Inverter remains lit. • In case of sufficient output power, the output will transfer to Inverter. • UPS output LED indicates Load on Inverter and the LCD must display on the main screen the status “LOAD ON INVERTER”. First operated unit All other units of the system 5. Press “inverter on” ( I ) key on all other Units.
8 OPTIONS 8.1 COMMUNICATION OPTIONS Advanced SNMP Card Simple Network Management Protocol The Advanced SNMP Card is an interface to the Ethernet Network, and provides UPS information via the standard SNMP Protocol (UPS-MIB (RFC-1628); GE Single MIB; GE Parallel MIB).
8.3 CONNECTION FOR OPTIONS WARNING ! The installation and cabling of the options must be performed by QUALIFIED SERVICE PERSONNEL only. Make sure that the UPS installation is completely powered down. Refer to the “Safety prescriptions - Installation” described on Section 1. 8.3.1 Remote Signalling Box (RSB) The optional Remote Signalling Box allows monitoring of the operation of the UPS, using the potential free contacts fitted on the “P4 - Customer Interface Board“ of the UPS.
9 MAINTENANCE WARNING ! All maintenance and service works must be performed by QUALIFIED SERVICE PERSONNEL. 9.1 MAINTENANCE A UPS system, like other electrical equipment, needs periodic preventive maintenance. A regular maintenance check of your installation guarantees higher reliability of your safe critical power supply. Preventive maintenance work on the UPS can be done only by trained Service technicians.
9.1.5 Long shut-down periods of the UPS-system To guarantee that the Battery is fully charged, the UPS system should be in operation for at least 12 hours every 3 months. If not the Battery may be permanently damaged. 9.1.6 UPS room conditions and temperature The UPS room and the Battery Room have to be maintained clean and free from dust. A high temperature of the UPS room and of the Battery Room affect the lifetime of several components inside the equipment.
10 NOTES 10.1 NOTES FORM It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc. Date Modifications reserved OPM_SGS_USM_M10_M15_0US_V030.