User's Manual

3
Control Drawing
Control Drawing, Pressure Scout
SignalFire Telemetry
Part
Name
Part
Number
Date
Page 1 of 1
960-0081-01
10/10/16
Rev
1.1
• WARNING: Substitution of components may impair intrinsic safety.
• Choose peripheral devices and associated apparatuses such that the following conditions are met:
Ui/Vmax ≥ Uo/Voc
Ii/Imax ≥ Io/Isc
Pi ≥ Po
Co/Ca ≥ Ci + Ccable
Lo/La ≥ Li + Lcable
• When replacing the internal battery, only use SignalFire lithium battery model number 810-0030-01 (1BIS)
• See SignalFire Instruction manuals numbers 960-0082-01 for installation requirements
• Install the internal battery pack only when external power is not used
J1
SignalFire Pressure Scout
Models: Scout-PSIx-y
x=pressure span, y=power source
Ambient Temperature Limit: -40C to +60C
Temperature Code: T3
Class I, Division 1, Groups C and D
BATTERY
Ui/Vmax: 5.9 VDC
Ii: 3.1 A
Pi: 0.89 W
Ci: 9.66 uF
Li: 0.1 uH
Power Source
PCB ASSY: 840-0133-01
SignalFire Telemetry
Rev 1.1