Operating instructions

Connect the stroke sensor to a suitable monitoring device according
to the technical data provided with the monitoring device and that of
the stroke sensor - see chapter "Technical data".
1. Install the cable which originates from the pacing relay - see the
figure in the chapter entitled "Overview of equipment and control
elements": Cable A, left.
The cable polarity is unimportant.
2. Install the power supply cable to the pacing relay PCB - see the
figure in the chapter entitled "Overview of equipment and control
elements": Cable B, right.
CAUTION!
Warning of overload
If the current through the relay becomes too high, it
can be destroyed by heating.
Fit a circuit breaker.
Pacing relay terminal output data
Data Value Unit
Maximum voltage 24 VDC
Maximum current 100 mA
Closing duration, approx. 100 ms
Service life *
50 x 10
6
(10 V,
10 mA)
Play
* at rated load
The contacts are potential-free.
The pacing relay is a N/O as standard.
Supply voltage for pacing relay PCB
Available supply vol‐
tages
Mains supply fre‐
quency
Power consumption
230 V AC (180-254 V) 50 / 60 Hz 10 mA (at 230 V, 50 Hz)
115 V AC (90-134 V) 50 / 60 Hz 15 mA (at 115 V, 60 Hz)
24 V DC (20-28 V) - 10 mA (at 24 V DC)
Install the other units according to their documentation.
Stroke sensor (identity code specification
"Stroke sensor": 3)
Pacing relay (identity code specification
"Stroke sensor": 2)
Other units
Installation
26