User Manual
Table Of Contents
- General Safety Summary
- Introduction of SDG2000X
- Quick Start
- Front Panel Operations
- To Set Sine Waveform
- To Set Square Waveform
- To Set Ramp Waveform
- To Set Pulse Waveform
- To Set Noise Waveform
- To Set DC Waveform
- To Set Arbitrary Waveform
- To Set Harmonic Function
- To Set Modulation Function
- To Set Sweep Function
- To Set Burst Function
- To Store and Recall
- To Set Utility Function
- Examples
- Example 1: Generate a Sine Waveform
- Example 2: Generate a Square Waveform
- Example 3: Generate a Ramp Waveform
- Example 4: Generate a Pulse Waveform
- Example 5: Generate a Noise
- Example 6: Generate a DC Waveform
- Example7: Generate a Linear Sweep Waveform
- Example 8: Generate a Burst Waveform
- Example 9: Generate an AM Modulation Waveform
- Example 10: Generate a FM Modulation Waveform
- Example 11: Generate a PM Modulation Waveform
- Example 12: Generate a FSK Modulation Waveform
- Example 13: Generate an ASK Modulation Waveform
- Example 14: Generate a PSK Modulation Waveform
- Example 15: Generate a PWM Modulation Waveform
- Example 16: Generate a DSB-AM Modulation Waveform
- Troubleshooting
- Service and Support
- Appendix
SIGLENT
SDG2000X User Manual 125
2.13.10 Overvoltage Protection
Choose Utility → Page 1/2 → OverVoltage Protection to turn on or off the function,
as shown in the following figure.
Figure 2-79 Overvoltage Protection Interface
If the state is set to ON, overvoltage protection of CH1 and CH2 will take effect
once any of the following conditions is met. When overvoltage protection
occurs, a message will be displayed and the output is disabled.
The absolute value of input voltage is higher than 11V±0.5V when the
amplitude of the generator is higher than or equal to 3.2Vpp or the DC
offset is higher than or equal to |2VDC|.
The absolute value of input voltage is higher than 4V±0.5V when the
amplitude of the generator is lower than 3.2Vpp or the DC offset is lower
than |2VDC|.