User Manual
Table Of Contents
- General Safety Summary
- Introduction of SDG2000X
- Quick Start
- Front Panel Operations
- To Set Sine Waveform
- To Set Square Waveform
- To Set Ramp Waveform
- To Set Pulse Waveform
- To Set Noise Waveform
- To Set DC Waveform
- To Set Arbitrary Waveform
- To Set Harmonic Function
- To Set Modulation Function
- To Set Sweep Function
- To Set Burst Function
- To Store and Recall
- To Set Utility Function
- Examples
- Example 1: Generate a Sine Waveform
- Example 2: Generate a Square Waveform
- Example 3: Generate a Ramp Waveform
- Example 4: Generate a Pulse Waveform
- Example 5: Generate a Noise
- Example 6: Generate a DC Waveform
- Example7: Generate a Linear Sweep Waveform
- Example 8: Generate a Burst Waveform
- Example 9: Generate an AM Modulation Waveform
- Example 10: Generate a FM Modulation Waveform
- Example 11: Generate a PM Modulation Waveform
- Example 12: Generate a FSK Modulation Waveform
- Example 13: Generate an ASK Modulation Waveform
- Example 14: Generate a PSK Modulation Waveform
- Example 15: Generate a PWM Modulation Waveform
- Example 16: Generate a DSB-AM Modulation Waveform
- Troubleshooting
- Service and Support
- Appendix
SIGLENT
106 SDG2000X User Manual
2.13.4 Output
Press Utility → Output to enter the following interface.
Figure 2-66 Output Setup Interface
Load
For the [CH1] and [CH2] connectors on the front panel, the generator has an
output impedance of 50Ω. If the actual load does not match the set load, the
displayed voltage will not be the same as the output voltage. This function is
used to match the displayed voltage with the expected one. This setting does
not actually change the output impedance to any other value.
Steps for setting the load:
Press Utility → Output Setup → Load, to set the output load. The load
parameter shown on the down bottom is the default setting when the power is
on or the pre-set load value.
High Impedance: displayed as HiZ;
Load: the default is 50Ω and the range is 50Ω to 100kΩ.
Note: