User's Manual

Model 3100 Series Flame Detector (11/04)
Page: 17
Instruction Manual
B.3 Verify/Aux. Relay Configurations
Model # Verify Relay Aux. Relay
3100-02 Open Contacts Closed Contacts
3100-03 Closed Contacts Open Contacts
3100-04 Open Contacts Open Contacts
3100-05 Closed Contact Closed Contacts
B.4 Fault Table
Fault # Fault Label Description
1 Lens Test Fault UV sensors didn’t detect enough UV from the internal UV source.
2 Configuration Fault SW9 is “ON” or a failed program
3 Calibration Fault Device is out of calibration
4 Volt. Low Input Voltage is below 15 VDC
5 Photo. Sensor Fault IR or Visible sensor failed to detect internal test source.
6 Relay Fault Relay coil circuit is open.
7 Volt. High Input Voltage was above 32 VDC
8 Temp. Out of Range Internal device temperature went below -40° C or above 85° C.
B.5 False Alarm Stimuli Table
FALSE ALARM RESPONSE
This table shows the detectors ability to tolerate both modulated and unmodulated false alarm stimuli.
False Alarms Source Distance Unmodulated Modulated
Resistive Electric Heater 1320 Watt 6 Feet No Response No Response
Fluorescent Lights (2) 40 Watt Bulbs 6 Feet No Response No Response
Halogen Light 500 Watt 10 Feet No Response No Response
Incandescent Light 100 Watt 6 Feet No Response No Response
Arc Welder 50 Watt 25 Feet No Response No Response
Direct Sunlight 93 million miles No Response No Response
B.6 Fire and False Alarm Stimuli Table
Model 3100 detector response to a fire while exposed to a variety of radiant energy sources.
False Alarms Distance to False Distance Response Time to
Source Alarm Source to Fire Fire
Resistive Electric Heater 1320 Watt 6 Feet 6 Feet Less than 5 sec.
Florescent Lights (2) 40 Watt Bulbs 6 Feet 6 Feet Less than 5 sec.
Halogen Light 500 Watt 10 Feet 6 Feet Less than 5 sec.
Incandescent Light 100 Watt 6 Feet 6 Feet Less than 5 sec.
Arc Welder 50 Watt 25 Feet 6 Feet Less than 5 sec.
Direct Sunlight 93 million miles 6 Feet Less than 5 sec.