User's Manual

Model 3100 Series Flame Detector (11/04)
Page: 15
Instruction Manual
APPENDIX B
TABLES
B.1 Dip Switch Settings
B.1.1 Sensitivity
Sensitivity SW1 SW2 Level
20 Foot ON ON 4
40 Foot OFF ON 3
60 Foot ON OFF 2
80 Foot OFF OFF 1
B.1.2 Verify Control (3100-02, -03, -04 and -05 Models only)
Verify Description SW3 SW4 SW5
Level 0 Verify = Fire OFF OFF OFF
Level 1 Min. Verify (shorter) ON OFF OFF
Level 2 Min. Verify (shorter) OFF ON OFF
Level 3 Min. Verify (shorter) ON ON OFF
Level 4 Min. Verify (shorter) OFF OFF ON
Level 5 Min. Verify (shorter) ON OFF ON
Level 6 Max. Verify (longer) OFF ON ON
Level 7 Verify Disabled ON ON ON
B.1.3 Fire Output“Latching” Control
Fire Output Description SW6
Latching Alarm until Power down Reset OFF
Following Alarm until no fire (.5 to 10 sec.) ON
B.1.4 Verify Relay “Latching” Control (3100-02, -03, -04 and -05 Models only)
Verify Relay Description SW7
Latching Alarm until Power down Reset OFF
Following Alarm until no fire (.5 to 10 sec.) ON
B.1.5 Detector "Non-Latching" Control
SW6, SW7 and SW8 must be on for the detector to be "Non-Latching".
B.1.6 Factory Use Only
SW8 and SW9 must be in the OFF position for normal operation. They are used for factory
calibration and testing.