Instruction manual
Model 5100-02-IT Combustible Gas Sensor Module 
Page: 38 
| 
|----▼ 4-20mA (Verifies 4mA or 20mA output and selects condition of output during calibration) 
|  | 
|   ▼ -------or--------------- E Calib 
|  |  |    
|    |  |- Out: 4mA 
|  |   | 
|  |   ▼ --or—E (To calibrate analog output 4mA, |▲ or ▼ to adjust level, 
|   |   |   then E t o accept) 
|  |   |- Out: 20mA   
|  |   ▼ --or--E (To calibrate analog output 20mA, |▲ or ▼ to adjust level, 
|   |   |   then E to accept) 
|  |   |- In: 4mA   
|  |   ▼ --or—E (To calibrate analog input 4mA, |▲ or ▼ to adjust level, 
|   |   |   then E to accept) 
|  |   |- In: 20mA   
|  |   ▼--or--E (To calibrate analog input 20mA, |▲ or ▼ to adjust level, 
|   |     then E to accept) 
|  |      
|   ▼ -------or--------------- E CalibOut (Adjust 4-20mA output during Calibration) 
|  |  |    
|    |  |- Track: (▲ or ▼ (To adjust action/mA value during calibration 
|    |     Track = mA value tracks Gas value 
|    |   Hold = holds mA value existing prior to calibration 
|    |   C1.50mA = 1.50 mA during calibration 
|    |   C4.00 mA = 4.00 mA during calibration 
|    |   User mA = |▲ or ▼ to adjust to desired mA value 
|  | 
|   ▼ -------or--------------- E Tbl Out (Adjust 4-20mA output during Trouble condition)     
|  |  | 
|    |  |- T2.50mA: (▲ or ▼ (To select 2.50mA or User mA, * = current value) 
|    |   User mA = |▲ or ▼ to adjust to desired mA value 
|  | 
|  | 
|----▼ RS-485 (Select RS-485 address and baud rate) 
|  | 
|    | - Address 
|  | 
|   ▼ | -------or--------------- E Addr:016 (Use (▲ or ▼ and E to select module address – 016 to 254) 
|  | 
|    |- Baud --------------- E *38400 (Use |▲ or ▼ and E to select baud rate, * = current selection) 
MAINT MENU
MAINT:: 
| 
E – V2.00aB (Software version installed on module) 
 | 
  E – CCC001 (Configuration number) 