Instruction manual
Model 5100-02-IT Combustible Gas Sensor Module 
Page: 37 
SETUP MENU 
Once in the SETUP menu use the ▲ or ▼ keys to access each of the 5 main sections of the SETUP menu. 
▼  ▼  ▼  ▼  ▼ 
| | | | |  
|- Alarms: |- Relays: |- GasFactr: |- 4-20mA: |-  RS-485 
SETUP: 
| 
E – Alarms (Alarms Set-Point Adjustment) 
| | 
|  E – H.Alarm (High Alarm Setup) 
|  | 
|  E --------------------------- OR---------------------------------------▼ 
|  |  | 
|    |- HASP: 60 (Current Hi Alarm set-point  |- L. ALARM (Low Alarm Setup) 
|  |  | 
|  ▲ or ▼ (To adjust to desired set-point)  E LASP:20 (Current Lo Alarm Set-point) 
|  |  | 
|  E – Ack (Accepts set-point)  ▲ or ▼ (To adjust to desired set-point) 
|   | 
|   E – Ack (Accepts set-point) 
|        
| 
|----▼ Relays (Relay Set Point Adjustment) 
| | 
|   E ----------------------------- OR-----------------------------------------▼: 
| |    | 
|  |- H. Relay (High Relay Setup)  |- L. Relay (Low Relay Setup) 
| |    | 
|  E – Latch  E – Latch 
| |    | 
|  ▲ or ▼ (To adjust to desired condition)  ▲ or ▼ (To adjust to desired condition) 
|      (Selections are Latch, NonLatc, or Senty) 
|      (* indicates current status, Sentry = Sentry controller controls alarm relay action) 
| 
|----▼ Gas Factr (Gas Factor Adjustment) 
| | 
|  E *Factr100 (* = current selection) 
|  | 
|  ▲ or ▼ (To adjust to desired factor) 
|        If USER is selected use the ▲ or ▼ keys to change to desired value 
| 