Instruction manual
Model 5100-02-IT Combustible Gas Sensor Module 
Page: 11 
6.  Carefully return the transmitter to the enclosure installing it over the two standoffs. Tighten the 
retaining screws into the standoffs. 
P1  FUNCTION  P2  FUNCTION 
1  High Alarm Relay NC  1  Power 
2  High Alarm Relay NO  2  Signal 
3  High Alarm Relay COM  3  Ground 
4  Low Alarm Relay NC  4  N/A 
5  Low Alarm Relay NO  5  N/A 
6  Low Alarm Relay COM  6  4-20 mA output - 
7  Trouble Relay NC*  7  4-20 mA output + 
8  Trouble Relay NO*  8  RS-485 Ground 
9  Trouble Relay COM  9  RS-485 (-) (B) 
10  Digital Input SW+  10  RS-485 (+) (A) 
11  Digital Input SW-     
*Trouble relay is fail safe so it is energized for normal operation. Functions 
are labeled for normal operation. 
Table 3-1 
Sensor Module External Interfaces 
7.  Establish the module address according to section 3.5. 
NOTE 
The warm-up period is 3 minutes from power on. 