Instruction manual

Model 5100-02-IT Combustible Gas Sensor Module
Page: 40
CommandSpecificResponseDataBytes:
Byte Format Description
01 Unsigned 16 ReturnscontentsofselectedModbusRegister
Command144:SetTransducerSerialNumber
Thiscommandallowsusertoaddadevicespecificserialnumber,ifrequired.Thisisdifferentfromtheserial
numberassignedbytheManufacturer.
RequestDataBytes:
Byte Format Description
02 Unsigned 24 SerialNumber
CommandSpecificResponseDataBytes:
Byte Format Description
02 Unsigned 16 ReturnsnewSerialNumber
Command145:SetCalibrationModeoutputcurrent
RequestDataBytes:
Byte Format Description
01 Unsigned 16 Currentoutputrequiredduringcalibration,in
microamperes
CommandSpecificResponseDataBytes:
Byte Format Description
01 Unsigned 16 ReturnsnewCalibrationcurrentvalue
Command146:SetTroubleModeoutputcurrent
RequestDataBytes:
Byte Format Description
01 Unsigned 16 CurrentoutputrequiredtoindicateTrouble,in
microamperes
CommandSpecificResponseDataBytes:
Byte Format Description
01 Unsigned 16 ReturnsnewTroublecurrentvalue
Command149:SetGasFactor
RequestDataBytes
Byte Format Description
0 Unsigned8 SetstheGasFactorvalue,range30to200