Instruction manual
Model 5100-02-IT Combustible Gas Sensor Module
Page: 40
CommandSpecificResponseDataBytes:
Byte Format Description
0‐1 Unsigned ‐16 ReturnscontentsofselectedModbusRegister
Command144:SetTransducerSerialNumber
Thiscommandallowsusertoaddadevicespecificserialnumber,ifrequired.Thisisdifferentfromtheserial
numberassignedbytheManufacturer.
RequestDataBytes:
Byte Format Description
0‐2 Unsigned ‐24 SerialNumber
CommandSpecificResponseDataBytes:
Byte Format Description
0‐2 Unsigned ‐16 ReturnsnewSerialNumber
Command145:SetCalibrationModeoutputcurrent
RequestDataBytes:
Byte Format Description
0‐1 Unsigned ‐16 Currentoutputrequiredduringcalibration,in
micro‐amperes
CommandSpecificResponseDataBytes:
Byte Format Description
0‐1 Unsigned ‐16 ReturnsnewCalibrationcurrentvalue
Command146:SetTroubleModeoutputcurrent
RequestDataBytes:
Byte Format Description
0‐1 Unsigned ‐16 CurrentoutputrequiredtoindicateTrouble,in
micro‐amperes
CommandSpecificResponseDataBytes:
Byte Format Description
0‐1 Unsigned ‐16 ReturnsnewTroublecurrentvalue
Command149:SetGasFactor
RequestDataBytes
Byte Format Description
0 Unsigned‐8 SetstheGasFactorvalue,range30to200