Instruction manual

Model 5100-02-IT Combustible Gas Sensor Module
Page: 38
CommandSpecificResponseDataBytes:
Byte Format Description
0 Unsigned8 ReturnsnewAlarmLevel.
Command132:SetWarningLevel
RequestDataBytes:
Byte Format Description
0 Unsigned8 Warninglevel,range0to60.Defaultis20.
CommandSpecificResponseDataBytes:
Byte Format Description
0 Unsigned8 ReturnsnewWarningLevel.
Command133:SetAlarmRelayAction
RequestDataBytes:
Byte Format Description
0 Unsigned80=Latching(default)
2=NonLatching
CommandSpecificResponseDataBytes:
Byte Format Description
0 Unsigned8 ReturnsnewAlarmRelayActionvalue
Command134:SetWarningRelayAction
RequestDataBytes:
Byte Format Description
0 Unsigned8 0=Latching
2=NonLatching(default)
CommandSpecificResponseDataBytes:
Byte Format Description
0 Unsigned8 ReturnsnewWarningRelayActionvalue
Command135:ResetAlarms
Thiscommandwillresetanyalarmrelaysthathavebeenlatched,providingthealarmconditionisnolonger
presentonthesensor.
RequestDataBytes:None
CommandSpecificResponseDataBytes: None
Command136:AbortCalibration
Thiscommandabortsthecalibrationprocedure.
RequestDataBytes:None
Command
SpecificResponseDataBytes: None