Instruction manual

Model 5100-02-IT Combustible Gas Sensor Module
Page: 33
Setting Up and Testing Model 5100-02-IT with Remote Sensor
1. Connect the remote module (p/n 5394-51) to Model 5100-02-IT.
2. Power up Model 5100-02-IT.
3. Connect the voltmeter from pin 4 to pin 3 of the connector (p/n 59201) (at the side connected to the
sensor).
4. Verify the voltage from pin 4 to pin 3 is 2 volts. If not, go to maintenance menu:
Hit M key 4 times to see Maint: display, then hit E key to enter Maintenance Menu
Hit Up Arrow key 5 times
Display shows V1 Diag
Hit Enter key
Hit Up Arrow key to see 2V Output display
5. Adjust the 2V Output (switch Up Arrow to increase, switch Down Arrow to decrease, and switch E key to
accept the change).
6. Repeat step 5 a few times to get 2 volts at pin 4 and pin 3 of the connector (2 volts is the bridge voltage of
the sensor).
7. Hit M key a few times to see EXIT display, then hit Enter.
8. Cycle the power.
9. Perform the calibration for Model 5100-02-IT.