Instruction manual
Model 5100-02-IT Combustible Gas Sensor Module 
Page: 24 
6. CALIBRATION 
6.1  CALIBRATION FREQUENCY 
The 5100-02-IT has been calibrated in the factory prior to shipment. It is recommended that the user check 
calibration before placing in service. The Combustible sensor module must be calibrated every 6 months. 
Periodic functional tests are advisable for critical applications and hostile environments.  
The sensor module microprocessor software includes high level self checking algorithms which provide 
continuous sensor diagnostic and self adjustment. Users may elect to increase calibration periods based on 
low drift experience during the first two calibration periods. 
6.2  CALIBRATION PREPARATION 
Calibration of the Combustible Sensor is accomplished by simple menu based steps and application of span 
gas.  
NOTE 
If an error is made during any stage of the calibration process, hold the magnet stick at the key 
M for 10 seconds. A scrolling display will indicate “Calibration aborted” and the sensor 
module will exit the calibration activity and return to normal operating mode. The calibration 
procedure can then be restarted 
Calibration must be performed only when the area is known to be clear of combustible gas. If necessary, use 
a portable instrument to confirm that there is no background combustible gas. 
For compliance with Factory Mutual (FM) Apparatus, the Sierra Monitor Model 1200-26, 1250-01, 1256-01,     
1260 -02 are the only FM Approved calibration gas delivery device. Use Model 5358-01 Calibration Adapter 
or Model 5360-00 Gas Delivery Fitting. 
6.3  CALIBRATION GAS DELIVERY METHODS 
Calibration gas is can be delivered to the sensors via the following delivery devices:  
Model 5358-01: Calibration Adapter - use with portable calibrators. See 6-1. 
Model 5360-00: Calibration Gas Delivery fitting - permanently installed fitting which 
allows tubing to be run to a convenient delivery location 
6.4  CALIBRATION PROCEDURE 
Table 6-1 shows the step by step process of the calibration procedure.  
The procedures requires that the menu “keys” be activated using the magnet stick.  
Each key press steps through the process of setting the zero value for clean air and 
then setting the span value. 
At each of these steps, apply calibration gas of the value corresponding to the setting 
accepted on the sensor module display. 
6.5  SENSOR EXPOSURE TO GAS 
Calibration gas must be delivered to the sensor using the flow rate and duration listed in below:  
Model Gas  Flow  Period 
5100-02-IT  Methane  300 cc/min   Until Stable – 3 minute minimum 
NOTE:  
Following calibration, the combustible module counts down for 300 seconds. During this time the module is updating its 
internal memory and it is very important that its power not be interrupted 
Figure 6 - 1: Model 
5358-01 Calibration 
Adapter 