Instruction manual
Model 5100-02-IT Combustible Gas Sensor Module
Page: 22
Table 5 - 3 B: Set-Up Configuration
M E
M E
M E
M E
M E
M E
M E
M E
ME
M E
M E
M E
ME
M E
ME
M E
M E
M E
M E
M E
M E
ME
M E
Enter *T1.50mA
Use
or
keys to select mA Valve between 0.5
and 3.7mA
Down User mA S.P. Function - User Selectable mA Valve
Enter *T1.50mA Current Valve 1.5mA for Trouble
Calib S.P. Function - Calib Adjust
Down Tbl Out S.P. Function - output during Trouble Alarm
Mode
Gas Factor Example
Enter GasFactr S.P. Function - Gas Factor Adjust *C
Enter Factr100
Select [E] to select or
or
to adjust factor
number and press [E]
Enter ACK Acknowledgement of new Gas Factor Value
4-20 mA Adjustment Example
Enter Calib S.P. Function - Calib Adjust *D
Enter Out: 4mA Use
or
keys to select 4 mA or 20mA
Enter 4mA Selects 4 mA
Enter ACK Momentary Acknowledge of new Set Point
Mode Calib S.P. Function - Calib Adjust
Down CalibOut S.P. Function - Output during Calibration Adjust
Use
or
keys to enter new address
Enter Track Use
or
keys to select Track, C2.5mA, C4.00mA
Track = Output during calibration tracks the calibration gas,
C2.5mA = Output during calibration is 2.5mA, C4.00mA =
Output during calibration is 4.0mA
Enter *T1.50mA Select 1.50mA for volume during trouble
Address S.P. Function - RS-485 Address Adjust
RS-485 Adjustment Example
Enter Address S.P. Function - RS-485 Address Adjust *E
Enter Addr:016
Enter *Track * = Current selection
Down
Enter ACK New address selected
Enter
Baud S.P. Function - RS-485 Baud Rate Adjust
Enter *38400 Press [E] to select or [
] or [
] to select another