Instruction manual
Model 5100-99-IT 4-20 mA Module 
 APPENDIX D: MODBUS MEMORY MAP 
Read Register Table 
Register  Description  Comments 
40001  Concentration  Gas Concentration multiplied by 100 
40002  Temperature  Temperature in degrees Celsius scaled by a factor of 100 
40003  High Alarm Relay  Boolean indicating the High Alarm Status, 0 No Alarm, 1 High Alarm 
40004  Low Alarm Relay  Boolean indicating the Low Alarm Status, 0 No Alarm, 1 Low Alarm 
40005  Low Alarm Value  Low alarm set point, used for activating Alarms 
40006  High Alarm Value  High alarm set point, used for activating High Alarms 
40007 Reserved   
40008 Reserved   
40009 Reserved   
40010 Reserved   
40011  Trouble Bits  0 for no trouble 
40012  Trouble  1 for any trouble, 0 for no trouble 
40013  High Alarm Immediate  Like 40003, but never latched 
40014  Low Alarm Immediate  Like 40004, but never latched 
40015  Random ID  Randomly generated permanent ID of sensor 
40016 Restart Count   
40017  Run time – high  In minutes 
40018  Run time – low  In minutes 
40019  Max. gas value  *scale (see 40024) 
40020  Model  51005, 51003, 51004, 51006, etc 
40021  Range  *scale (see 40024) 
40022  Units  3 is PPM 
40023  Temperature Units  0 is C, 1 is F 
40024  Gas Scale  Value like 1 or 100 
40025  Temperature Scale  Value like 1 or 100 
Page: 28 