Instruction manual
Model 5100-99-IT 4-20 mA Module
7. APPENDICES
APPENDIX A - SPECIFICATIONS
Output:
Display: Fixed and Scrolling LED
Relays (Optional): 8 Amp, High Alarm, Low Alarm, 2 Amp Trouble all SPDT
Analog Output (Optional) Analog 4-20 mA (Trouble 0 mA, Calibration 1.5 mA)
Signal Output: Sentry bus
Serial RS-485 Modbus RTU
Input:
Remote Alarm Reset: Normally open digital input (supervised or non-supervised)
Digital Input 4-20 mA
Analog Input
Electrical Data:
Power consumption: 2 watts
Connection type: 3 wire
Input voltage: 24 VDC nominal: 10-30VDC
Operating Range:
5100-99-IT
Ambient Temp (
o
F) 5 to 122
o
F
Ambient Temp (
o
C) -15 to 50
o
C
Relative Humidity 15 – 90%
Enclosure:
Material - Standard: Polyester powder-coated, sand-cast, copper-free aluminum
Material - Stainless Steel Option: 316 Stainless Steel
Enclosure Hazardous Location FM, ATEX, CSA
Approvals:
Dimensions: 5.28 x 4.9 x 4.76 inches Al & SS
(H x W x D) (10.56 x 9.8 x 9.52 cm)
Weight: 2.7 lb. (1.3 Kg) (standard Aluminum enclosure)
5.4 lb. (2.6 Kg) 316 Stainless Steel
Housing: NEMA 4X
Electrical Classification
FM Approved: Explosion proof, Class 1, Div. I, Groups B, C, D
Class I, Zone 1, Groups IIB+H2 IP66
Modbus:
Baud: 38400 (Adjustable 2400 to 38400 Baud)
Parity: None
Stop bit: 1
Data bits: 8
Flow Control: None
Memory map: Appendix E
Warranty: Limited Warranty 2 years
Specifications subject to change without notice
Ordering Information:
5100 - XX - IT - YY - ZZ
5100 Series -99=4-20mA - IT Series - Al (Aluminum Enclosure) - 01 Sentry, RS-485, 4-20mA, & Digital Input
- SS (Stainless Steel) - 02 = Sentry, RS-485, 4-20mA, Digital Input & Relays