Types
Power: Up to 40 W Up to 120 W CE
Control signal Protection mark
standard : IP31 IP54 IP31
DC 0 ... 10 V or ZM100/A ZM101/A ZM200/A Yes
DC 0 ... 20 V phase cut
DC 4 ... 20 mA or ZM120/A ZM121/A ZM220/A Yes
DC 0 ... 20 V phase cut
DC 0 ... 20 V phase cut ZM110 ZM111 ZM210 No
Technical data
Supply voltage
ZM100/A, ZM101/A, ZM120/A,
ZM121/A, ZM200/A, ZM220/A AC 24 V +15/–10 %, 50 ... 60 Hz
Extra-low voltage SELV / PELV
Current consumption Max. 1 mA at DC 0 ... 10 V
(Input impedance 2 x 56 kΩ)
Control signals (see "Types" above) DC 0 ... 10 V
DC 4 ... 20 mA
DC 0 ... 20 V phase cut
Shunt resistance (DC 4…20 mA) 150 Ω
Max. output power: (see "Types" above)
ZM1.. , ZM1../A Up to 40 W
ZM2.. , ZM2../A Up to 120 W
Mean operating power See valve data sheet
Housing material Aluminium
Connection terminals For 1 x 4 mm
2
or 2 x 2.5 mm
2
wire
Electrical safety Extra-low voltage SELV / PELV
Protection standards IP31 / IP54, see "Types" table
Ambient temperature:
ZM100/A, ZM110, ZM120/A 2 ... 50 °C
ZM101/A, ZM111, ZM121/A –40 ... 50 °C
ZM200/A, ZM210, ZM220/A 2 ... 50 °C
Dimensions: (and see page 3)
ZM1.. 40 x 60 x 76 mm
ZM2.. 40 x 90 x 115 mm
Weight:
ZM100/A, ZM111, ZM120/A 0.22 kg
ZM101/A, ZM121/A 0.24 kg
ZM110 0.20 kg
ZM200/A 0.44 kg
ZM210 0.38 kg
ZM220/A 0.46 kg
The ZM../A meets the requirements
for CE marking
ZM.. , ZM../A
Terminal housing for
magnetic valves
Terminal housing for optional
control of Landis & Staefa magnetic
valves with various control signals:
• DC 0 ... 10 V
• DC 4 ... 20 mA
• DC 0 ... 20 V phase cut
ZM.., ZM../A
4