10.1 Change mesh ID
Change the mesh ID if the blue LED on the RF converter is permanently
illuminated after installation and the web server is not switched on.
Proceed as follows:
Press buttons 2 and 3 at the same time for a few seconds. As soon you let go of
the buttons, one or all the green LEDs start flashing.
For a mesh ID ≥ 5, all the green LEDs flash simultaneously. Otherwise, only the
corresponding green LED flashes. For example, LED 1 flashes for a Mesh ID = 1.
Press button 3 for at least a second to change the mesh ID. The corresponding
green LED is on permanently as soon as the mesh ID is changed.
Press buttons 2 and 3 at the same time for more than a second to save the
changes.
Press button 2 to reject the changes.