Siemens M-bus level converter and M-bus web server A6V11157985_en--_f
Smart Infrastructure 2021-06-21
8.3 M-bus commissioning on web server
After installation and after all connections are established, the M-bus is
commissioned as per the following steps:
On the level converter, check that the M-bus Ready LED is on and the M-Bus
Error LED is off.
You must set the web server language the first time web server is activated. The
following languages are currently available:
German
English
Italian
French
Dutch
The language selected during the initial login applies to both the display as well as
the software user interface to web server. You can change the language after initial
login for the display and web server independently.
The display language can be changed anytime on the display.
See section “Select default operating language (Display)”, page 48.
You can change the language for the web server at any time in the software user
interface.
See Section 'Select the web server language (software interface)', page 65.
Define an 8-digit access code. Use the and navigation buttons to set a
number from 0…9. Press OK to go to the next digit.
You must reenter the 8-digit access code to confirm it.
The access code can be changed at any time to protect against unauthorized
access.
See section "Change access code", page 49.
In the Meter search main menu, start the search for connected M-bus devices.
Detailed information on the meter search workflow is available in section "Meter
search", page 97.
Check M
-
bus
First time log in
Notes
Access code
Change access code
Start meter search